List the parameter groups available to the drive and drive options.
Change parameter values.
e
3
0
b
g
2
7
2
.1
0
O-** Operation / Display
1-** Load and Motor
2-** Brakes
3-** Reference / Ramps
0 RPM 0.00 A
Main Menu
1(1)
Illustration 23: Main Menu View
For more detailed information on the menus or parameters, refer to the programming guide.
6.5 Entering System Information
The following steps are used to enter basic system information into the drive. Recommended parameter settings are intended for
start-up and checkout purposes. Application settings vary.
Although these steps assume that an induction motor is used, a permanent magnet motor can also be used. For more information
on specific motor types, see the product-specific programming guide.
N O T I C E
SOFTWARE DOWNLOAD
For commissioning via a PC, install VLT
®
Motion Control Tool MCT 10 set-up software. A basic version, which is sufficient for most
applications, is available for download. An advanced version, which can commission multiple drives at once, can be ordered.
See https://www.danfoss.com/en/service-and-support/downloads/?sort=title_asc&filter=download-type%3Dtools.
Procedure
Press [Main Menu] on the LCP.
Select
0–** Operation/Display
and press [OK].
Select
0–0* Basic Settings
and press [OK].
Select
parameter 0-03 Regional Settings
and press [OK].
Select
[0] International
or
[1] North America
as appropriate and press [OK]. (This action changes the default settings for some
basic parameters).
Press [Quick Menus] on the LCP and then select
02 Quick Setup
.
If needed, change the following parameter settings. Motor data is found on the motor nameplate.
Parameter 0-01 Language
(English)
Parameter 1-20 Motor Power
(4.00 kW)
Parameter 1-22 Motor Voltage
(400 V)
Parameter 1-23 Motor Frequency
(50 Hz)
Parameter 1-24 Motor Current
(9.00 A)
Parameter 1-25 Motor Nominal Speed
(1420 RPM)
Parameter 5-12 Terminal 27 Digital Input
(Coast Inverse)
Parameter 3-02 Minimum Reference
(0.000 RPM)
Parameter 3-03 Maximum Reference
(1500.000 RPM)
Parameter 3-41 Ramp 1 Ramp up Time
(3.00 s)
Parameter 3-42 Ramp 1 Ramp Down Time
(3.00 s)
Parameter 3-13 Reference Site
(Linked to Hand/Auto)
Parameter 1-29 Automatic Motor Adaptation
(Off)
AQ434333248451en-000101 / 130R1286 | 41
Danfoss A/S © 2023.01
Operating the Drive
VLT Ea4 Parallel Drive Modules
Operating Guide