![Danfoss VLT Ea4 Operating Manual Download Page 16](http://html1.mh-extra.com/html/danfoss/vlt-ea4/vlt-ea4_operating-manual_3870291016.webp)
•
•
•
•
•
1
2
3
4
5
e3
0b
f9
30
.1
1
Illustration 7: Unique Torque Values
1
All M4 fasteners [2.3 Nm (20 in-lb)]
2
3 M5 fasteners [3.9 Nm (35 in-lb)]
3
All gasketed M5 fasteners except door screws [3.9
Nm (35 in-lb)]
4
6 M5 fasteners attaching gate drive card [2.3 Nm (20
in-lb)]
5
All M5 fasteners attaching input plates to side
mounting rail [3.9 Nm (35 in-lb)]
–
–
4.2 Required Tools
Lifting equipment rated to lift the weight of the drive module
Drill with a 12 mm (1/2 in) drill bit
Tape measurer
Phillips and flat bladed screwdrivers
Wrench with 7–17 mm metric sockets and extensions
AQ434333248451en-000101 / 130R1286
16 | Danfoss A/S © 2023.01
Mechanical Installation
VLT Ea4 Parallel Drive Modules