Bit (Hex)
Extended status word (P. 541)
01 Ramping
04 Start clockwise/counterclockwise
08 Slow down
10 Catch-up
8000 Frequency limit
Table 4.8
Bit (Hex)
Alarm word (P. 538)
00000002 Trip lock
00000040 HPFB timeout
00000080 Standard bus timeout
00000100 Short circuit
00000200 24 V supply fault
00000400 Earth fault
00000800 Overcurrent
00004000 Motor thermistor
00008000 Inverter overload
00010000 Undervoltage
00020000 Overvoltage
00040000 Phase loss
00080000 Live zero error
00100000 Overtemperature
02000000 HPFB error
08000000 Inrush fault
10000000 Internal error
Table 4.9
4.3 List of Parameters
Parameter
No.
Function
Range/number of settings/
value
Factory setting
Data
type
Conv.
index
001
Language
6
English
5
0
002
Local/remote control
2
Remote control
5
0
003
Local reference
000.000
4
-3
004
Active Setup
4
Setup 1
5
0
005
Programming Setup
4
Active setup
5
0
006
Copying of Setups
4
No copying
5
0
007
LCP copy
4
No copying
5
0
008
Display scaling of motor frequency
100
6
-2
009
Display line 2
24
Frequency [Hz]
5
0
010
Display line 1.1
24
Reference [%]
5
0
011
Display line 1.2
24
Motor current [A]
5
0
012
Display line 1.3
24
Power [kW]
5
0
013
Local control/configuration
5
LCP digital control/par. 100 5
0
014
Local stop
2
Possible
5
0
015
Local jog
2
Not possible
5
0
016
Local reversing
2
Not possible
5
0
017
Local reset of trip
2
Possible
5
0
018
Lock for data change
2
Not locked
5
0
019
Operating state at power up, local c.
3
Forced stop, use saved ref.
5
0
Table 4.10 Functions to Programme, to Control and to Monitor via Bus (PROFIBUS) or by PC.
All about FCM 300
VLT
®
DriveMotor FCM Series
MG03BA02 - VLT
®
is a registered Danfoss trademark
89
4
4