Description of choice:
The jog frequency f
JOG
can be selected in the range
between f
MIN
(parameter 201) and f
MAX
(parameter 202).
512
Telegram profile
Value:
Fieldbus Profile (FIELDBUS PROFILE)
[0]
FC Profile (FC PROFILE)
[1]
Function:
There is a choice of two different control word profiles.
Description of choice:
Select the desired control word profile.
See
Serial communication
for further information about the
control word profiles.
513
Bus time interval
Value:
1-99 s
[1-99]
1 s
[1]
Function:
This parameter sets the maximum time expected to pass
between the receipt of two consecutive telegrams. If this
time is exceeded, the serial communication is assumed to
have stopped and the desired reaction is set in parameter
514.
Description of choice:
Set the desired time.
514
Bus time interval function
Value:
Off (OFF)
[0]
Freeze output (FREEZE OUTPUT)
[1]
Stop (STOP)
[2]
Jogging (JOGGING)
[3]
Max. speed (MAX SPEED)
[4]
Stop and trip (STOP AND TRIP)
[5]
Function:
This parameter selects the desired reaction of the FC
motor when the set time for bus timeout (parameter 513)
has been exceeded. If choices [1] to [5] are activated, relay
01 and relay 04 will be de-activated.
Description of choice:
The output frequency of the FC motor can: be frozen at
the present value, be frozen at the reference, go to stop,
go to jogging frequency (parameter 213), go to max.
output frequency (parameter 202) or stop and activate a
trip.
515
Data read-out: Reference %
Value:
XXX.X%
[XXXX]
Function:
This parameter can be read out via the serial communi-
cation port.
Description of choice:
The value shown corresponds to the total reference (sum
of digital/analogue/preset/bus/freeze ref./catchup and
slow-down).
This value is updated every 320 ms.
516
Data read-out: Reference unit
Value:
X.XXX Hz or rpm.
[XXXX]
Function:
This parameter can be read out via the serial communi-
cation port.
Description of choice:
Indicates the status value of the unit given on the basis of
the choice of the reference sum.
This value is updated every 320 ms.
517
Data read-out: Feedback
Value:
X.XXX
[XXXX]
Function:
This parameter can be read out via the serial communi-
cation port.
Description of choice:
Indicates the status value of terminals 1/2 at the unit/scale
selected in parameters 414 and 415.
This value is updated every 320 ms.
518
Data read-out: Frequency
Value:
XXX.X Hz
[XXXX]
Function:
This parameter can be read out via the serial communi-
cation port.
Description of choice:
The value shown corresponds to the actual motor
frequency.
This value is updated every 320 ms.
519
Data read-out: Frequency x scale
Value:
XXX.X Hz
[XXXX]
Function:
This parameter can be read out via the serial communi-
cation port.
Description of choice:
The value corresponds to the present output frequency f
M
multiplied by the factor preset in parameter 008
Display
scaling
of output frequency.
520
Data read-out: Current
Value:
XXX.XX A
[XXXXX]
Programming
VLT
®
DriveMotor FCM Series
MG03BA02 - VLT
®
is a registered Danfoss trademark
71
3
3
Summary of Contents for VLT Brook Crompton Motor FCM 300
Page 2: ......
Page 37: ...Programming VLT DriveMotor FCM Series MG03BA02 VLT is a registered Danfoss trademark 35 3 3...
Page 101: ...Index VLT DriveMotor FCM Series MG03BA02 VLT is a registered Danfoss trademark 99...
Page 102: ...www danfoss com drives MG03BA02 175R0087 MG03BA02 Rev 2011 12 22...