Function:
This parameter can be read out via the serial communi-
cation port.
Description of choice:
Indicates the status word transmitted via the serial
communication port.
537
Data read-out: INV. temperature
Value:
Unit: ºC
Function:
This parameter can be read out via the serial communi-
cation port.
Description of choice:
States the given temperature of the frequency converter.
This value is updated every 10 sec.
538
Data read-out: Alarm word
Value:
Unit
Function:
This parameter can be read out via the serial communi-
cation port. See
4.2.1 List of Warnings and Alarms
.
Description of choice:
States whether there is an alarm on the FC motor.
Hex
Fault messages
00000002
Trip lock
00000040
HPFB timeout
00000080
Standard bus timeout
00000100
Short circuit
00000200
24 V supply fault
00000400
Earth fault
00000800
Overcurrent
00004000
Motor thermistor
00008000
Inverter overload
00010000
Undervoltage
00020000
Overvoltage
00040000
Phase loss
00080000
Live zero error
00100000
Overtemperature
02000000
HPFB error
08000000
Inrush fault
10000000
Internal error
Table 3.34
539
Data read-out: Control word
Value:
Unit
Function:
This parameter can be read out via the serial communi-
cation port.
Description of choice:
Indicates the control word sent via the serial communi-
cation port in Hex code from the FC motor. This parameter
is updated every 20 ms.
540
Data read-out: Warning word
Value:
Unit
Function:
This parameter can be read out via the serial communi-
cation port. See
4.2.1 List of Warnings and Alarms
Description of choice:
States in Hex format whether there is a warning on the FC
motor.
Hex
Warning messages
00000008
HPFB timeout
00000010
Standard bus timeout
00000040
Current limit
00000200
Inverter overload
00001000
Voltage warning low
00002000
Voltage warning high
00004000
Phase loss
00010000
Live zero error warning
00400000
Output freq. limit warning
00800000
HPFB error
40000000
24 V supply warning
80000000
Inverter temp. high
Table 3.35
541
Data read-out: Extended status word
Value:
Unit
Function:
This parameter can be read out via the serial communi-
cation port.
Description of choice:
States in Hex format whether there is a warning on the FC
motor.
Hex
Status messages
01
Ramping
04
Start clockwise/counterclockwise
08
Slow down
10
Catch-up
8000
Frequency limit
Table 3.36
542
Data read-out: Terminal 1, analogue input
Value:
Unit: mA
Programming
VLT
®
DriveMotor FCM Series
MG03BA02 - VLT
®
is a registered Danfoss trademark
73
3
3