4.2 General Specifications
Mains supply (L1, L2, L3)
Supply terminals
L1, L2, L3
Supply voltage
380–480 V:-15% (-25%)
1)
to +10%
1) The frequency converter can run at -25% input voltage with reduced performance. The maximum output power of the
frequency converter is 75% in case of -25% input voltage and 85% in case of -15% input voltage.
Full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated supply voltage.
Supply frequency
50/60 Hz
±
5%
Maximum imbalance temporary between mains phases
3.0 % of rated supply voltage
True power factor (
λ
)
≥
0.9 nominal at rated load
Displacement power factor (cos
ϕ
)
near unity (
>
0.98)
Switching on input supply L1, L2, L3 (power-ups)
≤
7.5 kW
maximum 2 times/minute
Switching on input supply L1, L2, L3 (power-ups) 11–75 kW
maximum 1 time/minute
The unit is suitable for use on a circuit capable of delivering less than 100,000 RMS symmetrical Amperes, 480 V maximum.
Motor output (U, V, W)
Output voltage
0–100% of supply voltage
Output frequency
0–500 Hz
Output frequency in VVC
+
Mode
0–200 Hz
Switching on output
Unlimited
Ramp time
0.05–3600 s
Torque characteristics
Starting torque (constant torque)
maximum 160% for 60 s
1)
Overload torque (constant torque)
maximum 160% for 60 s
1)
Starting torque (variable torque)
maximum 110% for 60 s
1)
Overload torque (variable torque)
maximum 110% for 60 s
Starting current
maximum 200% for 1 s
Torque rise time in VVC
+
(independent of f
sw
)
10 ms
1) Percentage relates to the nominal torque.
2) The torque response time depends on application and load, but, as a general rule, the torque step from 0 to reference is 4–5 x
torque rise time.
Cable lengths and cross sections
1)
Maximum motor cable length, screened
50 m
Maximum motor cable length, unscreened
0.37–22 kW: 75 m, 30–75 kW: 100 m
Maximum cross section to control terminals, flexible/rigid wire
2.5 mm
2
/14 AWG
Minimum cross section to control terminals
0.55 mm
2
/ 30 AWG
1) For power cables, see Table 4.1 to Table 4.3.
Digital inputs
Programmable digital inputs
7
Terminal number
18, 19, 27
1)
, 29
1)
, 32, 33, 31
Logic
PNP or NPN
Voltage level
0–24 V DC
Voltage level, logic 0 PNP
< 5 V DC
Voltage level, logic 1 PNP
> 10 V DC
Voltage level, logic 0 NPN
> 19 V DC
Voltage level, logic 1 NPN
< 14 V DC
Maximum voltage on input
28 V DC
Pulse frequency range
4 Hz–32 kHz
(Duty cycle) mininum pulse width
4.5 ms
Input resistance, R
i
approximately 4 kΩ
1) Terminals 27 and 29 can also be programmed as output.
Specifications
Design Guide
52
Danfoss A/S © 09/2014 All rights reserved.
MG06B402
4
4