Bit 04, No error/error (no trip)
Bit 04=0: The frequency converter is not in fault mode.
Bit 04=1: The frequency converter shows an error but does
not trip.
Bit 05, Not used
Bit 05 is not used in the status word.
Bit 06, No error/triplock
Bit 06=0: The frequency converter is not in fault mode.
Bit 06=1: The frequency converter is tripped and locked.
Bit 07, No warning/warning
Bit 07=0: There are no warnings.
Bit 07=1: A warning has occurred.
Bit 08, Speed reference/speed=reference
Bit 08=0: The motor runs but the present speed is different
from the preset speed reference. It might, for example, be
the case when the speed ramps up/down during start/
stop.
Bit 08=1: The motor speed matches the preset speed
reference.
Bit 09, Local operation/bus control
Bit 09=0: [Off/Reset] is activated on the control unit or
local control
in
3-13 Reference Site
is selected. It is not
possible to control the frequency converter via serial
communication.
Bit 09=1: It is possible to control the frequency converter
via the fieldbus/serial communication.
Bit 10, Out of frequency limit
Bit 10=0: The output frequency has reached the value in
4-12 Motor Speed Low Limit [Hz]
or
4-14 Motor Speed High
Limit [Hz]
.
Bit 10=1: The output frequency is within the defined limits.
Bit 11, No operation/in operation
Bit 11=0: The motor is not running.
Bit 11=1: The frequency converter has a start signal
without coast.
Bit 12, Drive OK/stopped, autostart
Bit 12=0: There is no temporary overtemperature on the
frequency converter.
Bit 12=1: The frequency converter stops because of
overtemperature but the unit does not trip and resumes
operation once the overtemperature normalises.
Bit 13, Voltage OK/limit exceeded
Bit 13=0: There are no voltage warnings.
Bit 13=1: The DC voltage in the frequency converter’s
intermediate circuit is too low or too high.
Bit 14, Torque OK/limit exceeded
Bit 14=0: The motor current is lower than the current limit
selected in
4-18 Current Limit
.
Bit 14=1: The current limit in
4-18 Current Limit
is
exceeded.
Bit 15, Timer OK/limit exceeded
Bit 15=0: The timers for motor thermal protection and
thermal protection are not exceeded 100%.
Bit 15=1: One of the timers exceeds 100%.
RS485 Installation and Set-...
Design Guide
76