FC 300 Operating Instructions
How to Programme
4-** Limits / Warnings
Par.
No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
4-1* Motor limits
4-10
Motor speed direction
[2] Both directions
All set-ups
FALSE
-
Uint8
4-11
Motor speed low limit [RPM]
0 RPM
All set-ups
TRUE
67
Uint16
4-13
Motor speed high limit [RPM]
3600 RPM
All set-ups
TRUE
67
Uint16
4-16
Torque limit motor mode
160.0 %
All set-ups
TRUE
-1
Uint16
4-17
Torque limit generator mode
160.0 %
All set-ups
TRUE
-1
Uint16
4-18
Current limit
160.0 %
All set-ups
TRUE
-1
Uint16
4-19
Max output frequency
132.0 Hz
All set-ups
FALSE
-1
Uint16
4-5* Adj. warnings
4-50
Warning current low
0.00 A
All set-ups
TRUE
-2
Uint16
4-51
Warning current high
Par.
16-37
All set-ups
TRUE
-2
Uint16
4-52
Warning speed low
0 RPM
All set-ups
TRUE
67
Uint16
4-53
Warning speed high
Par.
4-13
All set-ups
TRUE
67
Uint16
4-58
Missing motor phase function
[0] Off
All set-ups
FALSE
-
Uint8
4-6* Speed bypass
4-60
Bypass speed from [RPM]
0 RPM
All set-ups
TRUE
67
Uint16
4-62
Bypass speed to [RPM]
0 RPM
All set-ups
TRUE
67
Uint16
*
default setting
( )
display text
[ ]
value for use in communication via serial communication port
39
MG.33.A2.02 - VLT is a registered Danfoss trademark