FC 300 Operating Instructions
How to Programme
Quick Transfer of Parameter Settings
Once the set-up of a drive is complete, we
recommend that you store the data in the LCP or on
a PC via MCT 10 Set-up Software Tool.
Data storage in LCP:
1.
Go to par. 0-50 LCP copy
2.
Press the [OK] key
3.
Select “All to LCP”
4.
Press the [OK] key
All parameter settings are now stored in the LCP indicated by the progress bar. When 100% is reached,
press [OK].
NB!:
Stop the unit before performing this operation.
You can now connect the LCP to another frequency converter and copy the parameter settings to this
frequency converter as well.
Data transfer from LCP to drive:
1.
Go to par. 0-50 LCP copy
2.
Press the [OK] key
3.
Select “All from LCP”
4.
Press the [OK] key
The parameter settings stored in the LCP are now transferred to the drive indicated by the progress bar.
When 100% is reached, press [OK].
NB!:
Stop the unit before performing this operation.
Reset to Default Setting
To restore all parameter values to their default setting go to par. 14-22
Operating Mode
and select
Initialisation. Power down the frequency converter. The frequency converter will automatically restore to
default settings during the next power up.
29