FC 300 Operating Instructions
How to Install
1.
Drill holes in accordance with the measurements given.
2.
You must provide screws suitable for the surface on which you want to mount the FC 300. Retighten
all four screws.
For installation of IP21/TYPE 1/IP4X top and bottom - see the Option Guide enclosed with the FC 300.
FC 300 IP20 allows side-by-side installation. Because of the need for cooling, there must be a minimum of
100 mm free air passage above and below the FC 300.
Electrical Installation
Connection to Mains and Earthing
NB!:
The plug connector for power can be
removed.
1.
Make sure the FC 300 is properly earthed.
Connect to earth connection (terminal 95). Use
screw from the accessory bag.
2.
Place plug connector 91, 92, 93 from the
accessory bag onto the terminals labelled MAINS
at the bottom of FC 300.
3.
Connect mains wires to the mains plug
connector.
The earth connection cable cross section
must be at least 10 mm
2
or 2 rated mains
wires terminated separately.
How to connect to mains and earthing.
NB!:
Check that mains voltage corresponds to
the mains voltage of the FC 300 name
plate.
13
MG.33.A2.02 - VLT is a registered Danfoss trademark