Enclosure
Door fan/Top fan airflow
Airflow over heatsink
IP21 / NEMA 1 &
IP54 / NEMA 12
D1 and D2
6,003 ft
3
/h [170 m
3
/h] (100 cfm)
27,015 ft
3
[765 m
3
/h] (450 cfm)
E1
12,006 ft
3
/h [340 m
3
/h] (200 cfm) 50,994 ft
3
/h [1,444 m
3
/h] (850 cfm)
IP21 / NEMA 1
F1, F2, F3 and F4
24,720 ft
3
/h [700 m
3
/h] (412 cfm)* 34,784 ft
3
/h [985 m
3
/h] (580 cfm)
IP54 / NEMA 12
F1, F2, F3 and F4
18,540 ft
3
/h [525 m
3
/h] (309 cfm)* 34,784 ft
3
/h [985 m
3
/h] (580 cfm)
IP00 / Chassis
D3 and D4
9,005 ft
3
/h [255 m
3
/h] (150 cfm)
27,015 ft
3
[765 m
3
/h] (450 cfm)
E2
9,005 ft
3
/h [255 m
3
/h] (150 cfm)
50,994 ft
3
/h [1,444 m
3
/h] (850 cfm)
* Airflow per fan. F enclosures contain multiple fans.
Table 3.2: Heatsink Air Flow
NOTE!
The fan runs for the following reasons:
1.
AMA
2.
DC Hold
3.
Pre-Mag
4.
DC Brake
5.
60% of nominal current is exceeded
6.
Specific heatsink temperature exceeded (power-size dependent).
Once the fan is started, it will run for a minimum of 10 minutes.
3.3.7 Installation on the wall - IP21 (NEMA 1) and IP54 (NEMA 12) Units
This only applies to D1 and D2 enclosures. Thought must be given to where the unit should be installed.
Take the relevant points into consideration before you select the final installation site:
•
Clearance space for cooling
•
Clearance for opening the door
•
Cable entry clearance from the bottom
Mark the mounting holes carefully using the mounting template on the wall, and drill the holes as indicated. Ensure proper distance to the floor and the
ceiling for cooling. A minimum of 8.9 in [225 mm] below the adjustable frequency drive is needed. Mount the bolts at the bottom and lift the adjustable
frequency drive up on the bolts. Tilt the adjustable frequency drive against the wall and mount the upper bolts. Tighten all four bolts to secure the
adjustable frequency drive against the wall.
3 How to Install
VLT
®
Automation Drive FC 300
Instruction Manual High Power
3-24
MG.33.U2.22 - VLT
®
is a registered Danfoss trademark