Power (kW)
Torque (Nm)
Enclo-
sure
200-240V
380-480V
525-600V
Mains
Motor
DC
connection
Brake
Earth
Relay
A2
1.1 - 3.0
1.1 - 4.0
1.1 - 4.0
1.8
1.8
1.8
1.8
3
0.6
A3
3.7
5.5 - 7.5
5.5 - 7.5
1.8
1.8
1.8
1.8
3
0.6
A4
1.1 - 2.2
1.1 - 4.0
1.8
1.8
1.8
1.8
3
0.6
A5
1.1 - 3.7
1.1 - 7.5
1.1 - 7.5
1.8
1.8
1.8
1.8
3
0.6
B1
5.5 - 11
11 - 18.5
11 - 18.5
1.8
1.8
1.5
1.5
3
0.6
B2
-
15
22
30
22
30
4.5
4.5
2)
4.5
4.5
2)
3.7
3.7
3.7
3.7
3
3
0.6
0.6
B3
5.5 - 11
11 - 18.5
11 - 18.5
1.8
1.8
1.8
1.8
3
0.6
B4
15 - 18.5
22 - 37
22 - 37
4.5
4.5
4.5
4.5
3
0.6
C1
18.5 - 30
37 - 55
37 - 55
10
10
10
10
3
0.6
C2
37 - 45
75 - 90
75 - 90
14/24
1)
14/24
1)
14
14
3
0.6
C3
22 - 30
45 - 55
45 - 55
10
10
10
10
3
0.6
C4
37 - 45
75 - 90
75 - 90
14/24
1)
14/24
1)
14
14
3
0.6
Table 10.15 Tightening of Terminals
1) For different cable dimensions x/y, where x
≤
95mm
2
and y
≥
95mm
2
.
2) Cable dimensions above 18.5kW
≥
35mm
2
and below 22kW
≤
10mm
2
.
Specifications
VLT
®
AQUA Drive
Operating Instructions
84
MG.20.M8.02 - VLT
®
is a registered Danfoss trademark
10