130B
T248.10
Illustration 2.13 Control Wiring Access for A2, A3, B3, B4, C3 and
C4 Enclosures
130B
T334.10
Illustration 2.14 Control Wiring Access for A4, A5, B1, B2, C1 and
C2 Enclosures
Please see
before tightening the covers.
Frame
IP20
IP21
IP55
IP66
A4/A5
-
-
2
2
B1
-
*
2.2
2.2
B2
-
*
2.2
2.2
C1
-
*
2.2
2.2
C2
-
*
2.2
2.2
* No screws to tighten
- Does not exist
Table 2.3 Tightening Torques for Covers (Nm)
2.4.5.2 Control Terminal Types
shows the removable frequency converter
connectors. Terminal functions and default settings are
summarized in
.
1
4
2
3
130BA012.11
61
68
69
39
42
50
53
54
55
12
13
18
19
27
29
32
33
20
37
Illustration 2.15 Control Terminal Locations
•
Connector 1 provides four programmable digital
inputs terminals, two additional digital terminals
programmable as either input or output, a 24V
DC terminal supply voltage, and a common for
optional customer supplied 24V DC voltage
•
Connector 2 terminals (+)68 and (-)69 are for an
RS-485 serial communications connection
•
Connector 3 provides two analog inputs, one
analog output, 10V DC supply voltage, and
commons for the inputs and output
•
Connector 4 is a USB port available for use with
the MCT-10
•
Also provided are two Form C relay outputs that
are in various locations depending upon the
frequency converter configuration and size
•
Some options available for ordering with the unit
may provide additional terminals. See the manual
provided with the equipment option.
See
for terminal ratings details.
Installation
VLT
®
AQUA Drive
Operating Instructions
16
MG.20.M8.02 - VLT
®
is a registered Danfoss trademark
2