Minimum required air speed and air volume for IP00
Voltage and frequency
AHF 005
AHF 010
380–415 V, 50 Hz
380–415 V, 60 Hz
440–480 V, 60 Hz
Power loss
Air speed
Air volume
Power loss
Air speed
Air volume
[A]
[A]
[W]
[m/s]
m³/s
[W]
[m/s]
[m³/s]
10
10
131
1)
1)
93
1)
1)
14
14
184
2
0.017
118
2
0.011
22
19
258
2
0.023
206
2
0.019
29
25
298
2
0.027
224
2
0.020
34
31
335
2
0.030
233
2
0.021
40
36
396
2
0.036
242
2
0.022
55
48
482
2
0.043
274
2
0.025
66
60
574
2
0.052
352
2
0.032
82
73
688
2
0.062
374
2
0.034
96
95
747
2
0.067
428
2
0.039
133
118
841
2
0.076
488
2
0.044
171
154
962
2
0.087
692
2
0.062
204
183
1080
2.5
0.097
743
2.5
0.067
251
231
1194
2.5
0.108
864
2.5
0.078
304
291
1288
2.5
0.116
905
2.5
0.082
325
355
1406
2.5
0.127
952
2.5
0.086
381
380
1510
2.5
0.136
1175
2.5
0.106
480
436
1852
2.5
0.167
1542
2.5
0.139
Table 4.2 Minimum Required Air Speed and Air Volume for IP00, 380–480 V, 50 Hz, and 60 Hz
1) Cooled by natural convection. No requirement for forced cooling.
Voltage and frequency
AHF 005
AHF 010
600 V, 60 Hz
500–690 V, 50 Hz
Power loss
Air speed
Air volume
Power loss
Air speed
Air volume
[A]
[A]
[W]
[m/s]
(m³/s)
[W]
[m/s]
[m³/s]
15
15
298
2
0.027
224
2
0.020
20
20
335
2
0.030
233
2
0.021
24
24
396
2
0.036
242
2
0.022
29
29
482
2
0.043
274
2
0.025
36
36
574
2
0.052
352
2
0.032
50
50
688
2
0.062
374
2
0.034
58
58
747
2
0.067
428
2
0.039
77
77
841
2
0.076
488
2
0.044
87
87
962
2
0.087
692
2
0.062
109
109
1080
2
0.097
743
2
0.067
128
128
1194
2
0.108
864
2
0.078
155
155
1288
2.5
0.116
905
2.5
0.082
197
197
1406
2.5
0.127
952
2.5
0.086
240
240
1510
2.5
0.136
1175
2.5
0.106
296
296
1852
2.5
0.167
1288
2.5
0.116
366
366
–
–
–
1542
2.5
0.139
395
395
–
–
–
1852
2.5
0.167
Table 4.3 Minimum Required Air Speed and Air Volume for IP00, 500–690 V, 50 Hz, and 600 V, 60 Hz
Requirements for Installati...
VLT
®
Advanced Harmonic Filter AHF 005/AHF 010
26
Danfoss A/S © 10/2016 All rights reserved.