5.2.2 Capacitor Disconnect Contactors
Selection table for VLT
®
Advanced Harmonic Filters AHF 005/AHF 010 using separate Danfoss contactors.
AHF current rating
AHF
enclosure
size
Danfoss contactors
380–415 V
50 Hz
380–415 V
60 Hz
440–480 V
60 Hz
600 V
60 Hz
500–690 V
50 Hz
AHF
005
AHF
010
AHF
005
AHF
010
AHF
005
AHF
010
AHF
005
AHF
010
AHF
005
AHF
010
Description
Ordering
number
[A]
[A]
[A]
[A]
[A]
[A]
[A]
[A]
[A]
[A]
Type
10
14
10
14
10
14
10
14
10
14
10
14
–
–
–
–
X1
CI 9
037H0021.32
22
29
22
29
22
29
22
29
19
25
19
25
–
–
–
–
X2
CI 16
037H0041.32
34
40
55
34
40
55
34
40
55
34
40
55
31
36
48
31
36
48
15
20
24
15
20
24
15
20
24
15
20
24
X3
CI 30
037H0055.32
66
82
66
82
66
82
66
82
60
73
60
73
29
36
29
36
29
36
29
36
X4
CI 45
037H0071.32
96
133
96
133
96
133
96
133
95
118
95
118
50
58
50
58
50
58
50
58
X5
CI 61
037H3061.32
171
204
171
204
171
204
171
204
154
183
154
183
77
87
109
128
77
87
109
128
77
87
109
128
77
87
109
128
X6
CI 98
037H3040.32
251
304
251
304
325
381
251
251
304
325
381
231
231
291
355
380
155
197
155
197
240
155
197
155
197
240
X7
CI 180
037H3082.31
325
381
–
304
325
381
–
291
355
380
–
240
296
296
366
240
296
296
366
X8
CI 180
037H3082.31
480
480
480
480
436
436
–
395
–
395
X8
CI 250
037H3267.32
Table 5.8 Selection Table, Capacitor Disconnect Contactors - Danfoss Types
5.2.2.1 Non-Danfoss Contactors
Non-Danfoss contactors are compatible with the VLT
®
Advanced Harmonic Filter AHF005/AHF 010. If using non-
Danfoss contactors for capacitor disconnect, always select
AC3-types. The current rating of the contactor must be
equal to or higher than 50% of the nominal current rating
of the AHF.
If the contactor is controlled by external equipment and
not by a specific parameter in a Danfoss frequency
converter, use contactors for capacitive switching.
5.3 Accessories
5.3.1 IP21/NEMA 1 Upgrade Kit
An upgrade kit is available for upgrading the VLT
®
Advanced Harmonic Filter AHF 005/AHF 010 from IP20 to
IP21/NEMA 1.
The kits consist of 2 parts:
•
A top plate that prevents dirt and vertically
falling drops of water from entering the filter.
•
A terminal box enclosing the terminals and
connections, thus ensuring touch-safe terminals.
The terminal cover is prepared for installation of a
contactor for capacitor disconnect.
Spacers must be used at IP21 top cover at enclosure sizes
with:
•
External fan type 1.
•
External fan type 2.
•
Internal fan type 2.
Selection of Advanced Harmo...
VLT
®
Advanced Harmonic Filter AHF 005/AHF 010
40
Danfoss A/S © 10/2016 All rights reserved.
MG80C502
5
5
Summary of Contents for VLT AHF 005
Page 2: ......