130BE831.10
3
4
4
1
2
1
Outlet for outgoing airflow
2
Inlet for ingoing airflow
3
AHF filter
4
Air baffles guiding the airflow through the filter
Illustration 4.11 Correct Installation in Deep and/or Wide
Cabinets - Air Baffles Force Airflow Through the Filter - Front
View
130BE069.10
1
4
4
2
3
1
Outlet for outgoing airflow
2
Inlet for ingoing airflow
3
AHF filter
4
Air baffles guiding the airflow through the filter
Illustration 4.12 Correct Installation in Deep and/or Wide
Cabinets - Air Baffles Force Airflow Through the Filter - Side
View
NOTICE
POSSIBLE INSUFFICIENT AIRFLOW
If the thermal switch activates repeatedly in IP00 instal-
lations, it is probably caused by insufficient airflow
through the filter.
•
Evaluate the airflow and the installation
conditions.
•
Make the required changes to provide proper
cooling.
For more information about overtemperature protection,
refer to
chapter 4.2.3 Overtemperature Protection
Requirements for Installati...