7 Specifications
7.1 General Specifications
7.1.1 General Technical Data
Supply voltage
380 V/60 Hz
400 V/50 Hz
460 V/60 Hz
600 V/60 Hz
690 V/50 Hz
Nominal supply voltages
380–415 V/60 Hz
380–415 V/50 Hz
440–480 V/60 Hz
600 V/60 Hz
500–690 V/50 Hz
Supply voltage tolerance
±
10%
Tolerances of the actual supply voltage
342–456 V/60 Hz
342–456 V/50 Hz
396–528 V/60 Hz
540–660 V/60 Hz
450–759 V/50 Hz
Supply frequency tolerance
+5% to -1.5%
Overload capability
160% for 60 s every 10 minutes
Efficiency
>0.98
THDi
1)
AHF 005 <5%
AHF 010 <10%
Cos
φ
of I
L
0.5 cap at 25% I
AHF,N
0.8 cap at 50% I
AHF,N
0.85 cap at 75% I
AHF,N
0.99 cap at 100% I
AHF,N
1.00 at 160% I
AHF,N
Power derating - temperature
5–45
°
C (41–113
°
F) without derating. 45–60
°
C (113–140
°
F) with derating 1.5% per
°
C. See
.
Power derating - altitude above sea level 1000 m (3280 ft) without derating. 1000–4000 m (3280–13123 ft) with derating 5% per 1000 m
(3280 ft).
Table 7.1 General Technical Data
1) THDi level is system level performance from the filter combined with the actual frequency converter.
NOTICE
The reduction of the low harmonic current emission to the rated THDi implies that the THDv of the non-influenced
mains voltage is lower than 2%, and the ratio of short circuit power to installed load (R
SCE
) is above 66. Under these
conditions, the THDi of the mains current of the frequency converter is reduced to 10% or 5% (typical values at nominal
load). If these conditions are not or only partially fulfilled, a significant reduction of the harmonic components can still
be achieved, but the rated THDi values may not be observed.
Specifications
Design Guide
MG80C502
Danfoss A/S © 10/2016 All rights reserved.
53
7
7