VLT
®
5000 FLUX
All about FCD
300
■
Tightening-up torques and screw sizes
The table shows the torque required when fitting
terminals to the frequency converter. For VLT
5001-5027 200-240 V and VLT 5001-5102 380-500
V, the cables must be fastened with screws. For VLT
5032-5052 200-240 V and VLT 5122-5500 380-500
V, the cables must be fastened with bolts.
These figures apply to the following terminals:
Mains terminals
Nos
91, 92, 93
L1, L2, L3
Motor terminals
Nos
96, 97, 98
U, V, W
Earth terminal
No
94, 95, 99
Brake resistor terminals
81, 82
Loadsharing
88, 89
VLT type
200-240 V
Torque [Nm]
Screw/
Boltsize
Tool
5001-5006
0,6
M3
Slotted screw
5008
IP20
1,8
M4
Slotted screw
5008-5011
IP54
1,8
M4
Slotted screw
5011-5022
IP20
3
M5
4 mm Allen wrench
5016-5022
3)
IP54
3
M5
4 mm Allen wrench
5027
6
M6
4 mm Allen wrench
5032-5052
1)
11,3
M8 (bolt and stud)
380-500 V
5001-5011
0,6
M3
Slotted screw
5016-5022
IP20
1,8
M4
Slotted screw
5016-5027
IP54
1,8
M4
Slotted screw
5027-5042
IP20
3
M5
4 mm Allen wrench
5032-5042
3)
IP54
3
M5
4 mm Allen wrench
5052-5062
6
M6
5 mm Allen wrench
5072-5102
IP20
15
M6
6 mm Allen wrench
IP54
2)
24
M8
8 mm Allen wrench
5122-5302
4)
19
M10 bolt
5350-5500
5)
42
M12 bolt
1) Brake terminals: 3,0 Nm, Nut: M6
2) Brake and loadsharing: 14 Nm, M6 Allen screw
3) IP54 with RFI - Line terminals 6Nm, Screw: M6 - 5 mm Allen wrench
4) Loadshare and brake terminals: 9,5 Nm; Bolt M8
5) Brake terminals: 11,3 Nm; Bolt M8
MG.55.A6.02 - VLT is a registered Danfoss trademark
21