VLT
®
5000 FLUX
PNU
Parameter
Factory setting
Range
Changes
4-Setup
Conversion
Data
#
description
during operation
index
type
100
Configuration
Speed control, closed loop
No
Yes
0
5
101
Torque characteristics
High - constant torque
No
Yes
0
5
102
Motor power
Depends on the unit
0.18-500 kW
No
Yes
1
6
103
Motor voltage
Depends on the unit
200 - 500 V
No
Yes
0
6
104
Motor frequency
50 Hz
No
Yes
0
6
105
Motor current
Depends on the unit
0.01-I
VLT,MAX
No
Yes
-2
7
106
Rated motor speed
Depends on the unit
100-60000 rpm
No
Yes
0
6
107
Automatic motor adaptation, AMA Adaptation off
No
No
0
5
115
Slip Compensating
100%
-400% - +400%
Yes
Yes
0
3
116
Slip compensation time constant
0.50 sec.
0.05-5.00 sec.
Yes
Yes
-2
6
119
High starting torque
0.0 sec.
0.0 - 0.5 sec.
Yes
Yes
-1
5
120
Start delay
0.0 sec.
0.0 - 10.0 sec.
Yes
Yes
-1
5
121
Start function
Coasting in start delay time
Yes
Yes
0
5
122
Function at stop
Coasting
Yes
Yes
0
5
123
Min. speed for activating function
at stop
0 rpm
0 - 600 rpm
Yes
Yes
-1
5
124
DC holding current
50 %
0 - 100 %
Yes
Yes
0
6
125
DC braking current
50 %
0 - 160 %
Yes
Yes
0
6
126
DC braking time
10.0 sec.
0.0 - 60.0 sec.
Yes
Yes
-1
6
127
DC brake cut-in speed
Off
0.0-par. 202
Yes
Yes
-1
6
128
Motor thermal protection
No protection
Yes
Yes
0
5
129
External motor fan
No
Yes
Yes
0
5
130
Start speed
0.0 rpm
0.0 - 600 rpm
Yes
Yes
-1
5
131
Initial current
0.0 Amp
0.0-par. 105
Yes
Yes
-1
6
150
Stator resistance
Depends on unit
Ohm
No
Yes
-4
7
151
Rotor resistance
Depends on unit
Ohm
No
Yes
-4
7
152
Stator leakage reactance
Depends on unit
Ohm
No
Yes
-3
7
153
Rotor leakage reactance
Depends on unit
Ohm
No
Yes
-3
7
154
Main reactance
Depends on unit
Ohm
No
Yes
-3
7
156
Pole number
4-pole motor
2-100
No
Yes
0
5
158
Ironloss resistance
10000
1 - 10000
No
Yes
0
6
161
Minimum Inertia
Depends on unit
Kgm
2
No
Yes
-4
7
162
Maximum Inertia
Depends on unit
Kgm
2
No
Yes
-4
7
163
Functional stop delay
0
0 – 5 sec
Yes
Yes
-1
7
164
Mech. brake release delay
0.5 sec
0.01 - 2.00 sec
Yes
Yes
-2
U16
165
Mech. brake initial torque
20%
+/- P221
Yes
Yes
-1
S16
166
Mech. brake initial direction
[0] Clockwise
[0] Clockwise
[1] Ref. dir.
Yes
Yes
0
U8
167
Proportional gain boost, during
brake release
100%
0-400%
Yes
Yes
0
S16
See also
Operation and Display
for further
information regarding Changes during operation,
4-Setup and Conversion index.
MG.55.A6.02 - VLT is a registered Danfoss trademark
132