Reliable galvanic isolation: All encoder inputs are galvanically isolated from the supply voltage (PELV). In
addition, encoder inputs can be isolated from the other terminals on the control card by connecting an
external 24 V DC supply and opening switch 4. See section on Control cables.
Control card, digital/pulse outputs:
No. of programmable digital outputs ..................................................................................................................... 2
Terminal nos. ................................................................................................................................................ 26, 46
Voltage level at digital/pulse output ...................................................................................................... 0 - 24 V DC
Minimum load to ground (terminal 39) at digital/pulse output ....................................................................... 600
Frequency ranges (digital output used as pulse output) .................................................................... 100HZ-50 kHz
Refresh time ................................................................................................................................................... 3 ms
Accuracy .................................................................................................................................. ±0.1% of full range
Galvanic isolation: All digital outputs are galvanically isolated from the supply voltage
(PELV) as well as other inputs and outputs.
Control card, analog outputs:
No. of programmable digital outputs ..................................................................................................................... 2
Terminal nos. ................................................................................................................................................ 42, 45
Current range at analog output ............................................................................................................ 0/4 - 20 mA
Maximum load to ground (terminal 39) at analog output ............................................................................... 500
Accuracy of analog output ............................................................................................ Max. error: 1% of full scale
Resolution on analog output ............................................................................................................................ 8 bit
Galvanic isolation: All analog outputs are galvanically isolated from the supply voltage
(PELV) as well as other inputs and outputs.
Control card, 24 V DC supply:
Terminal nos. ................................................................................................................................................ 12, 13
Max. load (short-circuit protection) ............................................................................................................. 200 mA
Terminal nos. ground .................................................................................................................................... 20, 39
Reliable galvanic isolation: The 24 V DC supply is galvanically isolated from the supply voltage
(PELV), but has the same potential as the analog outputs.
Control card, RS 232 / RS 485 serial communication:
RS 232 ........................................................................................................................................ RJ-11 connector
Terminal nos. .............................................................................................................. 68 (TX+, RX+), 69 (TX-, RX-)
Full galvanic isolation.
Relay outputs:
No. of programmable relay outputs ...................................................................................................................... 2
Terminal nos., control card ..................................................................................................................... 4-5 (make)
Max. terminal load (AC) on 4-5, control card ..........................................................................
50 V AC, 1 A, 60 VA
Max. terminal load (DC-1, IEC847) on 4-5, control card ....................................................... 75 V DC, 0.1 A, 30 W
Max. terminal load (DC-1, IEC947) on 4-5, control card for UL/cUL applications
..... 30 V AC, 1 A / 42.5 V DC, 1A
Terminal nos., power card ................................................................................................... 1-3 (break), 1-2 (make)
Max. terminal load (AC) on 1-3, 1-2, power card .................................................................
240 V AC, 2 A, 60 VA
Max. terminal load (DC-1, IEC947) on 1-3, 1-2, power card .............................................................. 50 V DC, 2 A
Min. terminal load on 1-3, 1-2, power card ........................................................ 24 V DC 10 mA, 24 V AC 100 mA
Brake resistor terminals (only SB, EB, DE and PB units):
Terminal nos. ................................................................................................................................................ 81, 82