Expose the shield of all 3 cables to make a 360° connection with the grounding clamp for cable shield.
e3
0b
h2
82
.1
0
8.
Make sure that the grounding conductor is connected to the motor and also to the terminals that are identified with the PE symbol.
A
To comply with the requirements of the standard EN 61800-5-1, obey the instructions in
.
B
Connect the protective conductor to one of the screw connectors with a cable shoe and an M8 screw.
Electrical Installation
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711
52 | Danfoss A/S © 2019.05