10.3.5 Cable and Fuse Sizes, Mains Voltage 525–690 V, North America
Table 27: Cable and Fuse Sizes, Mains Voltage 525–690 V, North America
Enclosure
size
Drive type
I
L
[A]
Fuse (Class
T/J) [A]
Mains, motor
and brake re-
sistor
(1)
cable
Cu [AWG]
Mains terminal cable size
[AWG]
Grounding terminal cable
size [AWG]
MR5 (600
V)
0004 6
3.9
6
14
20–6
17–8
0006 6
6.1
10
14
20–6
17–8
0009 6
9.0
10
14
20–6
17–8
0011 6
11.0
15
14
20–6
17–8
MR6
0007 7
7.5
10
12
13–0
13–2
0010 7
10.0
15
12
13–0
13–2
0013 7
13.5
20
12
13–0
13–2
0018 6
0018 7
18.0
20
10
13–0
13–2
0022 6
0022 7
22.0
25
10
13–0
13–2
0027 6
0027 7
27.0
30
8
13–0
13–2
0034 6
0034 7
34.0
40
8
13–0
13–2
MR7
0041 6
0041 7
41.0
50
6
9–2/0
9–2/0
0052 6
0052 7
52.0
60
6
9–2/0
9–2/0
0062 6
0062 7
62.0
70
4
9–2/0
9–2/0
MR8
0080 6
0080 7
80.0
90
1/0
1 AWG–350 kcmil
1 AWG–350 kcmil
0100 6
0100 7
100.0
110
1/0
1 AWG–350 kcmil
1 AWG–350 kcmil
0125 6
0125 7
125.0
150
2/0
1 AWG–350 kcmil
1 AWG–350 kcmil
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711| 111
Danfoss A/S © 2019.05