10.6.10 Power Ratings of VACON® 100 HVAC, 380–500 V
Table 40: Power Ratings of VACON
®
100 HVAC, Mains Voltage 380–500 V, 50–60 Hz, 3~
Enclo-
sure
size
Drive type
(1)
Low Loadability:
Continuous current
I
L
[A]
(2)
Low Loadability:
Input current I
in
[A]
(2)
Low Loadabili-
ty: 10% over-
load current [A]
(2)
Motor shaft power
(3)
: 10% overload
40°C [kW]
Motor shaft
power
(3)
: 10%
overload 40°C
[hp]
MR4
0003
3.4
3.4
3.7
1.1
1.5
0004
4.8
4.6
5.3
1.5
2.0
0005
5.6
5.4
6.2
2.2
3.0
0008
8.0
8.1
8.8
3.0
5.0
0009
9.6
9.3
10.6
4.0
5.0
0012
12.0
11.3
13.2
5.5
7.5
MR5
0016
16.0
15.4
17.6
7.5
10.0
0023
23.0
21.3
25.3
11.0
15.0
0031
31.0
28.4
34.1
15.0
20.0
MR6
0038
38.0
36.7
41.8
18.5
25.0
0046
46.0
43.6
50.6
22.0
30.0
0061
61.0
58.2
67.1
30.0
40.0
MR7
0072
72.0
67.5
79.2
37.0
50.0
0087
87.0
85.3
95.7
45.0
60.0
0105
105.0
100.6
115.5
55.0
75.0
MR8
0140
140.0
139.4
154.0
75.0
100.0
0170
170.0
166.5
187.0
90.0
125.0
0205
205.0
199.6
225.5
110.0
150.0
MR9A
0261
261.0
258.0
287.1
132.0
200.0
0310
310.0
303.0
341.0
160.0
250.0
1
The currents in given ambient temperatures are achieved only when the switching frequency is the same or smaller than the factory default.
2
See
.
3
230 V
10.7 Overload Capability
The
low overload
means that if 110% of the continuous current (I
L
) is required for 1 minute every 10 minutes, the remaining 9 minutes
must be approximately 98% of I
L
or less. This is to make sure that the output current is not more than I
L
during the duty cycle.
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711
124 | Danfoss A/S © 2019.05