RZ1 AND RZ1-HP
12
GB
5.1 Initiating a primary controller shift in an
undefined network using RZ1
Should you wish to carry out a controller shift before a network has
been set-up this will be available by following the steps below:
1. With the
PROG LED
flashing
GREEN
, push the
PROG
button for
at least 12 seconds.
2. The
PROG LED
will turn solid
ORANGE
to indicate that the
controller shift mode has been activated.
3. Press and release the
CH1
button and the
PROG LED
will flash
RED
slowly to indicate that a controller shift is occurring.
4. Start the inclusion process on the controller to be added to the
network as a replacement primary controller.
5. If the process is successful, the
PROG LED
will show solid
RED
,
failure will be indicated by the
PROG LED
flashing
ORANGE
.
6. To return to normal
RUN
mode, press the
PROG
button, the
LED
will show
GREEN
.
7. If the process has failed, press and release the
PROG
button,
the
PROG LED
will show solid
RED
and the process can be
repeated.
A network primary controller shift can not be started if:
1. The RZ1/RZ1-HP has created the network and is the existing
primary, as it is the networks SIS by default.
2. The RZ1/RZ1-HP is a secondary network controller and not the
SUC and no other SIS is in the network.
If a user attempts to do a controller shift and points 1 and 2 apply the
process will fail automatically.
For the different methods of initiating a primary controller shift
please see the rest of section 5.
5.0 Implementing a network controller shift