CAN message (continued)
Sent by
configuration tool
Sent to
PVED-CL
Data field
Bytes
Encoding
Value/Range
Description
1, 2
UNSIGNED16
0x0FA6 (MSB first)
extended message identifier (XID)
3
UNSIGNED8
0x5A
check value
CommitDataResponse
Sent back to signal any change in the commit process status.
This means the CommitData command may result in several responses, e.g. ready > in progress >
succeeded.
The minimum delay between responses is set to 40 ms.
CAN message
Priority
6
PGN
61184
XID
0x0FA7 (MSB first)
Occurrence
upon request
Modes
operational, reduced, calibration
Sent by
PVED-CL
Sent to
configuration tool
Data field
Bytes
Encoding
Value/Range
Description
1, 2
UNSIGNED16
0x0FA7 (MSB first)
extended message identifier (XID)
3
UNSIGNED8
0x00
0x01
0x02
0x03
0x04
0x05
Commit status:
– ready to perform commit operation
– commit operation has just begun
– the operation succeeded
– the operation failed
– parameter cross-check failed
– commit is already in progress
4, 5
UNSIGNED16
Commit error code
If commit operation failed, an error code on the
particular parameter cross-check is issued.
If commit operation succeeded, the value is 0.
Please refer to
Commit Error Code
on page 37.
EnterCalibrationMode
This command is used to force PVED-CL to enter the calibration mode, for further information see
PVED-
CL User Manual
, 11079550 and shall be sent within 200ms after PVED-CL transmits its Address Claimed
message.
Once the system state changes to Calibration, a response – GetCurrentModeResponse with a proper
mode identifier – will be sent back.
Technical Information
PVED-CL Communication Protocol, version 1.38 Technical Information
Configuration
20