background image

refrigerant flow and pressure drops (sol
enoid valve, filter dryer, expansion valve, etc.),
refrigerant charge.

·

 Low refrigerant charge : The correct refriger-

ant charge is given by the liquid sight glass indica-
tion, the condenser delta T in relation to the refrig-
erant pressure tables (pressure-temperature), the su-
perheat  and the sub-cooling, etc. ((if additional
charge is deemed necessary, refer to the “Filling
the system
” section).

·

 Compressor short cycling : The number of

cycles shall never exceed 12 starts per hour.

12 - Maintenance

·

 Performer

®

 compressors do not necessitate

any special maintenance procedure. However, it
must be recalled that proper operations and main-
tenance of the system serve to prevent against
system-related compressor problems. The follow-
ing preventive maintenance checks, to be per-
for med at regular intervals, are highly
recommended:

o Control operating conditions (evaporating
temperature, condensing temperature, com-
pressor discharge temperature, temperature
difference on heat exchangers, superheat,
sub-cooling). These conditions must always
remain within compressor operation limits.
o Verify that safety devices are operational
and properly set.
o Check the compressor oil level and
quality; this step may include an acid test,
humidity check, spectrometer analysis, etc.
whenever the oil becomes discolored.
o Ensure that the circuit is leak tight.
o Verify the proper operation of heat exchangers
and, if necessary, clean them.
o Check the current draw on the
compressor motor as well as proper voltage
balance between phases.
o  Check that all electrical connections are
still adequately fastened.
o Make sure the compressor is clean and in
good working order; verify the absence of rust
on the compressor shell, piping and electrical
connections.
o Make sure the refrigerant charge is suitable
for both winter and summer operation.

·

 Ensure that periodic in-service inspections

required by local regulations are performed.

13 – Replacement

Precaution must be taken when  disconnecting,

cutting or drilling holes in the tubing to ensure that
no refrigerant under pressure is present in the
system.

The refrigerant shall not be discharged

directly into the atmosphere; rather, it must be
removed using approved reclamation techniques
and equipment and then safely stored, in accordance
with applicable legislation.

The presence of refrigerant vapor can dis-

place air and lead to suffocation. Proper ventila-
tion is mandatory at all times when servicing the
equipment.

A refrigeration system component change

must be carried out in compliance with local
regulations.

·

 Make sure that the main power supply has been

switched  off.

·

 Before replacement, it is necessar y to

determine the cause of failure and implement
remedial action. If such analysis and repair are
not performed, repetitive failure may occur.
Note  that an oil acidity test always proves helpful in

8510197P01-D         © Danfoss Maneurop 

 

06-2002

5

Instructions

diagnosis when undertaking compressor replacement.

·

 Check that the new Performer

®

 compressor

and the on-site compressor to be replaced dis-
play the same electrical and refrigeration perfor-
mance characteristics.

·

 Use the rubber grommets and gaskets sup-

plied with the new compressor.

·

 Whenever piping needs to be modified, please

refer to the “Safety measures prior to assembly
section.

·

 For further details on replacement steps, refer

to the previous sections of this manual.

Note: In  the event of motor failure, flush and clean
the entire circuit before replacing the compressor
in order to remove acids and contaminants.
Systematically install a new filter dryer on the
liquid line. Prior to this step (if necessary), run the
system for at least 2 hours with anti-acid
cartridges (in such instances, the installation of a
suction filter might also be required). After an
operating period of approximately 2 weeks, check
the level of oil acidity. If the oil acid test proves
positive, drain and replace the oil, replace the
anti-acid liquid line filter dryer cartridges and the
suction filter previously installed. Repeat oil and
filter dryer replacements until the system is clean
and acid-free. When there is no longer any sign of
acidity, replace the anti-acid cartridges by the stan-
dard model and remove the suction strainer car-
tridge as required.

14 - User advisory

I

nsist that all service operations only be

performed by qualified personnel.

The compressor and tubing surface tempera-

tures may exceed 100

°

C (212

°

F) and cause se-

vere bodily burns. Special precaution must be
taken when working around the compressor and
refrigerant tubing. Moreover, a compressor in
operation can generate very cold surface tempera-
tures (as low as -25

°

C / -13

°

F), thereby exposing

personnel to the risk of freezing burns.

Pressure inside the compressor can reach

dangerously high levels (e.g. abnormal operation,
fire,…) leading to personnel injury if suddenly
released; therefore, never drill, weld or cut the com-
pressor shell and adjacent tubing (release of liq-
uid refr igerant can cause flash freezing on
exposed skin).
Be aware that the product warranty may be
deemed null and void in the following cases:

·

 external modifications to the compressor

(absence of nameplate, drilling, welding, broken
feet, shock marks),

·

 compressor opened by the user or returned

unsealed (i.e. open discharge or suction ports),

·

 presence of rust or water inside the compres-

sor

·

 addition of leak-detection fluid in the lubricant

·

 use of a refrigerant or lubricant not approved

by Danfoss Maneurop S.A.,

·

 any deviation from recommended instructions

pertaining to installation, application or maintenance,

·

 use in mobile applications (boats, trains, trucks,

etc.) or under explosive atmospheric conditions
(the compressor connecting box is not
explosion-proof).
The date of production of the compressor is
indicated on the nameplate. Ensure that
the model and serial number  information is
always transmitted with any claim filed regarding
this product.

10 - Start up

Never start the compressor in the absence

of a refrigerant charge.

·

 Do not bypass the LP or any other safety

switches during start-up.

·

 Check current draw and voltage levels.

·

 Monitor the oil sight glass (when mounted) for

60 min. to ensure proper oil return to the compressor.

·

 Suction superheat setting: Optimal compres-

sor suction superheat would be around 10K, with
the maximum allowable superheat being 30K.

·

 In all cases, the application limits of the

compressor must be respected; moreover, high
superheat  values lead  to high discharge
temperatures and decrease compressor capacity.
The maximum discharge temperature is 130

°

C :

operating at a higher temperature may result in
refrigerant decomposition.

·

 Under steady-state operating conditions, check

refrigerant piping or capillary tubes for abnormal
vibrations (refrigeration line movement in excess
of 1.5 mm necessitates corrective actions, pipe
brackets, etc.).

·

 After 2 to 4 hours of operations under

established  conditions, check the oil level and
add oil if necessary (refer to TI bulletin  1-025).
If oil return continues to perform poorly, fur ther
investigation of the piping design is required.

·

 Ensure that refrigerant flow through the liquid

line sight glass (when mounted) is adequate and
that operating temperatures correspond with
system specifications.

·

 When needed, refrigerant may be added in the

liquid phase, carefully throttling the refrigerant on
the low-pressure side and as far as possible from
the compressor. The compressor must be
operating during this process.

Do not overcharge the system

.

11 – Troubleshooting

·

  Compressor failure to start: Verify that the

compressor is hooked up to the power supply;
check the power lead connections. If these
verifications reveal no abnormality, control the
motor windings with an ohmmeter.
Note: When the internal motor protector has
tripped out (SM/SZ 084 -090- 100 - 110 - 120 -
161), it may take up to several hours to reset and
restart the compressor.

·

  Compressor failure to build up pressure:

Check to make sure that all bypass valves in the
system have not been open. Also check that all
solenoid valves are in their proper position.
For S240 and S300 models, if the internal
pressure relief valve is opened, the compressor
sump will be warm and the compressor will trip
out on the motor protector. If this happens, it may
take up to 2 or 3 hours to reset.

·

 Abnormal running noise: Ensure the absence

of any liquid flood-back to the compressor by
means of measuring the return gas superheat and
compressor

 

sump temperature. The sump should

be at least 10K above the saturated suction
temperature under steady-state operating conditions.

·

  The high-pressure switch trips out: Check

condenser operations (condenser cleanliness, fan
operations, water flow and water pressure valve,
water filter, etc.). If above check out OK, the prob-
lem may be due to either refr igerant over
charging or the presence of a non-condensable
(e.g. air) in the circuit.

·

  The low-pressure switch trips out: Check

evaporator operations (coil cleanliness,fan
operations, water flow, water filter, etc.), liquid

Summary of Contents for Performer SZ R407C

Page 1: ...01 D Danfoss Maneurop 06 2002 Fig 1 INSTRUCTIONS INSTRUKTION Fig 3 Fig 2 1 3 4 5 6 Fig 5 Fig 4 1 2 3 4 5 6 HP LP OIL OIL OIL OIL LP HP U trap Evaporator 8 to 12 m s max 4m max 4m 0 5 0 5 4m s LP HP LP...

Page 2: ...0 5 10 15 20 25 20 15 10 5 0 5 10 15 20 20 15 10 5 0 5 10 15 20 25 20 15 10 5 0 5 10 15 70 65 60 55 50 45 40 35 30 75 70 65 60 55 50 45 40 35 30 70 65 60 55 50 45 40 35 30 75 70 65 60 55 50 45 40 35 3...

Page 3: ...essor connection fittings it is mandatory to connect a 1 4 service hose to the Schrader fitting on the compressor shell in order to gradually release the nitrogen holding charge Ensure that no materia...

Page 4: ...er current protection an external manual reset overload protector must be used Note that Performer compressors SM SZ 084 090 100 110 120 161 are protected against overheating and overloading by an int...

Page 5: ...g surface tempera tures may exceed 100 C 212 F and cause se vere bodily burns Special precaution must be taken when working around the compressor and refrigerant tubing Moreover a compressor in operat...

Page 6: ...0 5 10 15 20 25 20 15 10 5 0 5 10 15 20 20 15 10 5 0 5 10 15 20 25 20 15 10 5 0 5 10 15 70 65 60 55 50 45 40 35 30 75 70 65 60 55 50 45 40 35 30 70 65 60 55 50 45 40 35 30 75 70 65 60 55 50 45 40 35 3...

Page 7: ...bjet d une r clamation adress e au transporteur Les m mes recommandations s appliquent aux cas de non respect des instructions de transport Veuillez lire soigneusement les consignes de s curit imprim...

Page 8: ...r lorsque le circuit est sous vide risque de court circuit du moteur claquage moteur 7 Connexions lectriques V rifiez que l alimentation lectrique principale du syst me a t coup e et isol e conform me...

Page 9: ...our les pressions maximum de s curit du compresseur L utilisation d un pressostat de s curit basse pression est recommand e pour emp cher un fonctionnement sous vide R glage minimum recommand 1 1 bar...

Page 10: ...changeurs de chaleur surchauffe sous refroidissement Ces param tres de fonctionnement doivent toujours se situer dans la plage d utilisation du compresseur o V rifiez que les dispositifs de s curit so...

Page 11: ...5 10 15 20 25 20 15 10 5 0 5 10 15 20 20 15 10 5 0 5 10 15 20 25 20 15 10 5 0 5 10 15 70 65 60 55 50 45 40 35 30 75 70 65 60 55 50 45 40 35 30 70 65 60 55 50 45 40 35 30 75 70 65 60 55 50 45 40 35 30...

Page 12: ...Positi on mit dem Kopf nach unten kann seine Funkti onst chtigkeit nicht gew hrleistet werden Bitte beachten dass alle Handhabungen des Verdichters mit u erster Sorgfalt erfolgen sollen um St e zu ve...

Page 13: ...tolock Anschlusses mit der L tbuchse ist die Teflondichtung zu entfernen und darauf zu achten dass die urspr nglichen Saug und Ausgangsdichtungen ersetzt werden m ssen Bei der Installation von Rotoloc...

Page 14: ...ten Inbetriebnahme und oder nach l ngeren Stillstandsperioden eingeschaltet wird 10 Inbetriebnahme Keinesfalls den Verdichter ohne K ltemittel bef llung starten Weder der Niederdruck noch irgend ein a...

Page 15: ...sverfahren und ausr stungen entfernt und anschlie end sicher gelagert werden K ltemitteld mpfe k nnen die Luft verdr n gen und zu Erstickungsgefahr f hren Deshalb ist bei Servicearbeiten an der Anlage...

Page 16: ...other material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes b...

Reviews: