Input
Type
Range
Description
Enbl_ResetTest
BOOL
——
Determines if the I/O module volatile memory is periodically checked to ensure the device has
not lost volatile configuration information due to temporary loss of power.
T: Volatile information is requested from the I/O module and compared every 1 second.
F: Volatile memory is not checked after initialization and temporary loss of power to the I/O
module may go undetected.
BusRecvryTm
U16
0–65535
BusRecvryTm sets the time the I/O module CAN port waits after going into a “bus off” condition
before attempting to go back on the bus.
1000 is 1 ms.
DriverRecvryTm
U16
0–65535
DriverRecvryTm sets the time the I/O module CAN port waits after a CAN error causes the
driver to reset before attempting to go back on the bus.
1000 is 1 ms.
RepTime_Supply
U16
0–65535
Determines how often the Power, Sensor Power, and CAN Shield input values are transmitted
from the I/O module.
1000 is 1 ms.
RepTime_Status
U16
0–65535
Determines how often the Output Status values are transmitted from the I/O module.
1000 is 1 ms.
RepTime_Outputs U16
0–65535
Determines how often the Output values are transmitted to the I/O module.
1000 is 1 ms.
TimeOut_Outputs U16
0–65535
Sets the maximum time allowed between commands for each output. If a command is not
received by the I/O module before the TimeOut_Outputs elapses then that output reverts to its
default output value and default pin configuration.
1000 is 1 ms.
Inputs – Power Supply
The status of power supply input on the connector and pin C1p02 is described.
Signal
Type
Direction
Range
Description
C1p02_Pwr
Bus
——
——
AnIn U16
Input
0 – 32767
Analog input AD count.
Due to CAN message optimization, this value is approximated by scaling the Volt
signal.
Volt U16
Input
0 – 36000
Analog input voltage
100 is 100 mV.
Updated BOOL
Input
——
True when the AnIn and Volt signals are refreshed.
Inputs – CAN Shield
The status of analog and CAN0 shield inputs on the connector and pin C1p05 is described.
Signal
Type
Direction
Range
Description
C1p05_AnIn
Bus
——
——
AnIn U16
Input
0 – 32767
Analog input AD count.
Due to CAN message optimization, this value is approximated by scaling the Volt
signal.
Volt U16
Input
0 – 5250
Analog input voltage.
100 is 100 mV.
Updated BOOL
Input
——
True when the AnIn and Volt signals are refreshed.
User Manual
PLUS+1® Compliant OX024-x10 Function Block
OX024-x10 Function Block
©
Danfoss | July 2018
11063395 | AQ00000104en-US0101 | 5