background image

Fixed Addressing Mode
Fixed addressing mode allows for any pair of CAN message identifiers to be used for I/O module

communication.

In this mode, the I/O module relies on the RX_ID, TX_ID, and Frame parameters for communication with
the function block. Use the PLUS+1

®

 Service Tool to set the proper values to match the function block and

to set the AddrMode.

Volatile Parameters
Once initial communication is established, all volatile parameter configuration messages are sent to the

I/O module.

Non-Volatile Parameters
After volatile parameters are configured, the function block sends a request for the configuration CRC to

the I/O module.

If this number matches the locally calculated value, then the configurations stored on the I/O module
match those set in the function block. If the numbers do not match, then all configuration commands are
sent and the CRC is requested again.

You can use the PLUS+1

®

 Service Tool to access all non-volatile parameters on the I/O module.

Timing Configurations
Timing for messages to and from the I/O module is established after all other configurations are sent.

CAN Bus Load
Adjust the average amount of message transmissions on the CAN bus to allow for bursts and other

increased message transmission situations.

Any CAN bus has a maximum message transmission capacity. So, to allow for situations that can cause
increases in messages, minimize the CAN bus load.

The CAN bus load is the average amount of message transmission on a CAN bus. Use the PLUS+1

®

 CG150

USB/CAN gateway and CANKing software to view CAN bus loads.

PLUS+1

®

 I/O modules communicate with their associated controllers over a CAN bus. System developers

can adjust I/O module RepTime and TimeOut parameters to manage CAN bus loading. Increasing these
times reduces the CAN bus load. Decreasing these times increases CAN bus load.

CAN Message Identifiers

The function block uses the following message identifiers to enable communication between the

controller and the I/O module.

I/O Module CAN Message Identifiers

CAN Shield Voltage [mV]

N1

KWP2000 Node

Tx ID

Rx ID

0 – 299

0

0

0x180

0x300

300 – 599

1

8

0x188

0x308

600 – 899

2

16

0x190

0x310

900 – 1199

3

24

0x198

0x318

1200 – 1499

4

32

0x1A0

0x320

1500 – 1799

5

40

0x1A8

0x328

1800 – 2099

6

48

0x1B0

0x330

User Manual

PLUS+1® Compliant OX024-x10 Function Block

OX024-x10 Function Block

 

©

 Danfoss | July 2018

11063395 | AQ00000104en-US0101 | 11

Summary of Contents for OX024-x10

Page 1: ...User Manual PLUS 1 Compliant OX024 x10 Function Block www danfoss com...

Page 2: ...Revision history Table of revisions Date Changed Rev July 2018 Rebranding 0101 July 2016 BA User Manual PLUS 1 Compliant OX024 x10 Function Block 2 Danfoss July 2018 11063395 AQ00000104en US0101...

Page 3: ...ts 7 Inputs CAN 8 Connections and Signal Overview 9 Configure Communications Between Controller and I O Module 10 Variable Addressing Mode 10 Predefined Addressing Mode 10 Fixed Addressing Mode 11 Vol...

Page 4: ...g Tx ID and Rx ID The CAN messages use either 11 bit or 29 bit identifiers in this mode as determined by Frame Tx ID U32 0x00 0x1FFFFFFF Tx ID is the CAN message identifier used by the function block...

Page 5: ...n the Output values are transmitted to the I O module 1000 is 1 ms TimeOut_Outputs U16 0 65535 Sets the maximum time allowed between commands for each output If a command is not received by the I O mo...

Page 6: ...Out True Updated BOOL Input True when the Volt and PinStatus signals are refreshed Inputs MFOut Output Status The input status of multifunction outputs on connectors and pins C1p12 C2p01 C2p02 C2p03 C...

Page 7: ..._MFOut Bus Config Bus PinConfig U16 Output 0 8 Output pin configuration 0 Digital Output Push Pull 1 Digital Output Sourcing 2 Digital Output Sinking 3 PWM Output 0 10000 0 01 positive duty 4 PWM Outp...

Page 8: ...ckCRC 6 Waiting for CRC response Outputs are disabled except for RecheckCRC 7 The I O module is properly configured and in the normal operational state Outputs are enabled 8 The function block s outpu...

Page 9: ...is used in an application each block requires unique Inputs and Outputs bus connections For example IO_Bus IO_Bus1 IO_Bus2 are needed User Manual PLUS 1 Compliant OX024 x10 Function Block OX024 x10 Fu...

Page 10: ...de must be set to 0 Every time the device is powered the CAN shield input voltage must be within the same N1 range for the function block and device to reach the Configured status After the device is...

Page 11: ...ns are sent CAN Bus Load Adjust the average amount of message transmissions on the CAN bus to allow for bursts and other increased message transmission situations Any CAN bus has a maximum message tra...

Page 12: ...e the proper addressing mode and corresponding communication parameters are set on both the I O module and the function block It is possible the I O module is correctly configured but a second I O mod...

Page 13: ...User Manual PLUS 1 Compliant OX024 x10 Function Block Danfoss July 2018 11063395 AQ00000104en US0101 13...

Page 14: ...User Manual PLUS 1 Compliant OX024 x10 Function Block 14 Danfoss July 2018 11063395 AQ00000104en US0101...

Page 15: ...User Manual PLUS 1 Compliant OX024 x10 Function Block Danfoss July 2018 11063395 AQ00000104en US0101 15...

Page 16: ...lutions ApS Nordborgvej 81 DK 6430 Nordborg Denmark Phone 45 7488 2222 Danfoss Power Solutions US Company 2800 East 13th Street Ames IA 50010 USA Phone 1 515 239 6000 Danfoss Power Solutions Trading S...

Reviews: