background image

 •  Braze with great care using state-of-the-art tech-

nique and vent piping with nitrogen gas flow.

 •  Connect the required safety and control de-

vices. When the schrader port is used for this, 

remove the internal valve.

 •  It is recommended to insulate the suction pipe 

up to the compressor inlet with 19 mm thick 

insulation.

5 – Leak detection

 Never pressurize the circuit with oxygen or 

dry air. This could cause fire or explosion.

 •  Do not use dye for leak detection.

 •  Perform a leak detection test on the complete 

system.

 •  The maximum test pressure is 32 bar.

 •  When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration
 •  Never use the compressor to evacuate the system.

 •  Connect a vacuum pump to both the LP & HP 

sides.

 •  Pull down the system under a vacuum of 500 

μm Hg (0.67 mbar) absolute.

 •  Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 

this may cause internal damage.

7 – Electrical connections
 •  Switch off and isolate the main power supply.

 •  Ensure that power supply can not be switched 

on during installation.

 •  All electrical components must be selected as 

per local standards and unit requirements.

 •  Refer to wiring diagram for electrical connec-

tions details.

 •  Ensure that the power supply corresponds 

to the unit characteristics and that the power 

supply is stable (nominal voltage ±10% and 

nominal frequency ±2,5 Hz).

 •  Dimension the power supply cables according 

to unit data for voltage and current.

 •  Protect the power supply and ensure correct 

earthing.

 •  Make the power supply according to local stan-

dards and legal requirements.

 •  The unit is equipped with high and low pressure 

switches, which directly cut the power supply to 

the compressor in case of activation. Parameters 

for high and low pressure cut outs should be 

set by installer considering compressor model, 

refrigerant and application. Units with Danfoss 

MLZ and LLZ compressors are also equipped 

with phase sequence relay to protect the unit 

against phase loss/sequence/ asymmetry and 

under-/over-voltage.

For units with a 3-phase scroll compressor, cor-

rect phase sequence for compressor rotation 

direction shall be observed.

 •  Determine the phase sequence by using a 

phase meter in order to establish the phase 

orders of line phases L1, L2 and L3.

 •  Connect line phases L1, L2 and L3 to main swit-

ch terminals T1, T2 and T3 respectively.

8 – Filling the system
 •  Wear protective stuff like goggles and protec-

tive gloves.

 •  Never start the compressor under vacuum. 

Keep the compressor switched off.

 •  Before charging the refrigerant, verify that the 

oil level is between ¼ and ¾ on the compressor 

oil sight glass. If additional oil is required please 

refer to the compressors label for type of oil.

 •  Use only the refrigerant for which the unit is 

designed for.

 •  Fill the refrigerant in liquid phase into the 

condenser or liquid receiver. Ensure a slow 

charging of the system to 4 – 5 bar for R404A / 

R507A or R22 and approx. 2 bar for R134a.

 •  Do not put liquid refrigerant through suction line.

 •  It is not allowed to mix additives with the oil 

and/or refrigerant

 •  The remaining charge is done until the instal-

lation has reached a level of stable nominal 

condition during operation.

 •  Never leave the filling cylinder connected to 

the circuit.

9 – Verification before commissioning

 Use safety devices such as safety pressure 

switch and mechanical relief valve in compliance 

with both generally and locally applicable regu-

lations and safety standards. Ensure that they 

are operational and properly set.

 Check that the settings of high-pressure swit-

ches and relief valves don’t exceed the maximum 

service pressure of any system component.

 •  Verify that all electrical connections are properly 

fastened and in compliance with local regulations.

 •  When a crankcase heater is required, it must be 

energized at least 12 hours before initial start-

up and start-up after prolonged shut-down 

period.

10 – Start-up
 •  Never start the unit when no refrigerant is char-

ged.

 •  All service valves must be in the open position.

See picture 3.

 •  Check compliance between unit and power 

supply.

 •  Check that the crankcase heater is working.

 •  Check that the fan can rotate freely.

 •  Check that the protection sheet has been re-

moved from the backside of condenser.

 •  Balance the HP/LP pressure.

 •  Energize the unit. It must start promptly. If 

the compressor does not start, check wiring 

conformity, voltage on terminals and sequence 

phase.

 •  Eventual reverse rotation of  a 3-phase com-

pressor can be detected by following phe-

nomena; unit doesn’t start, the compressor 

doesn’t build up pressure, it has abnormally 

high sound level and abnormally low power 

consumption. In such case, shut down the unit 

immediately and connect the phases to their 

proper terminals.

 •  If the rotation direction is correct the low pres-

sure indication on the low pressure gauge shall 

show a declining pressure and the high pres-

sure indication on the high pressure gauge 

shall show an increasing pressure.

11 – Check with running unit
 •  Check the fan rotation direction. Air must flow 

from the condenser towards the fan.

 •  Check current draw and voltage.

 •  Check suction superheat to reduce risk of slug-

ging.

 •  When a sight glass is provided observe the oil 

level at start and during operation to confirm 

that the oil level remains visible.

 •  Respect the operating limits.

 •  Check all tubes for abnormal vibration. Move-

ments in excess of 1.5 mm require corrective 

measures such as tube brackets.

 •  When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side as 

far away as possible from the compressor. The 

compressor must be operating during this pro-

cess.

 •  Do not overcharge the system.

 •  Never release refrigerant to atmosphere.

 •  Before leaving the installation site, carry out 

a general installation inspection regarding 

cleanliness, noise and leak detection.

 •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference 

for future inspections.

12 – Maintenance

 Always switch off the unit at main switch 

before remove fan panel.

 Internal pressure and surface temperature 

are dangerous and may cause permanent injury.

Maintenance operators and installers require 

appropriate skills and tools. Tubing temperature 

may exceed 100°C and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 

regulations are performed.

To prevent system related problems, following

Periodic  maintenance is recommended:

 •  Verify that safety devices are operational and 

properly set.

 •  Ensure that the system is leak tight.

 •  Check the compressor current draw.

 •  Confirm that the system is operating in a way 

consistent with previous maintenance records 

and ambient conditions.

 •  Check that all electrical connections are still 

adequately fastened.

 •  Keep the unit clean and verify the absence of 

rust and oxidation on the unit components, 

tubes and electrical connections.

The condenser must be checked at least once 

a year for clogging and be cleaned if deemed 

necessary. Access to the internal side of the 

condenser takes place through the fan panel. 

Microchannel coils tend to accumulate dirt on 

the surface rather than inside, which makes 

them easier to clean than fin-&-tube coils.

 •  Switch off the unit at main switch before re-

move any panel from the condensing unit.

 •  Remove surface dirt, leaves, fibres, etc. with 

a vacuum cleaner, equipped with a brush or 

other soft attachment. Alternatively, blow com-

pressed air through the coil from the inside out, 

and brush with a soft bristle. Do not use a wire 

brush. Do not impact or scrape the coil with the 

vacuum tube or air nozzle.

If the refrigerant system has been opened, the 

system has to be flushed with dry air or nitrogen 

to remove moisture and a new filter drier has to

be installed. If evacuation of refrigerant has to be 

done, it shall be done in such a way that no refri-

gerant can escape to the environment.

13 - Warranty
Always transmit the model number and serial num-

ber with any claim filed regarding this product.

The product warranty may be void in following 

cases:

 •  Absence of nameplate.

 •  External modifications; in particular, drilling, 

welding, broken feet and shock marks.

 •  Compressor opened or returned unsealed.

 •  Rust, water or leak detection dye inside the 

compressor.

 •  Use of a refrigerant or lubricant not approved 

by Danfoss.

 •  Any deviation from recommended instructions 

pertaining to installation, application or main-

tenance.

 •  Use in mobile applications.

 •  Use in explosive atmospheric environment.

 •  No model number or serial number transmit-

ted with the warranty claim.

14 – Disposal
Danfoss recommends that condensing 

units and oil should be recycled by a 

suitable company at its site.

Instructions

© Danfoss | DCS (CC) | 2017.02  | 5

FRCC.PI.051.A1.03

Summary of Contents for OP-HPMP

Page 1: ...English English p 4 Español Spanish p 9 Português do Brasil Brazilian Portuguese p 14 Instructions Optyma Slim Pack OP HPMP HPZP HPUS LPZP LPZS 1 Danfoss DCS CC 2017 03 FRCC PI 051 A1 ML ...

Page 2: ...880 525 327 361 Ø8 861 30 OP HPMP036 40 OP HPZP036 40 OP HPUS019 21 327 861 626 51 361 Ø8 525 30 OP HPMP019 28 OP HPZP019 28 OP HPUS015 LPZP048 68 Instructions 2 Danfoss DCS CC 2017 03 FRCC PI 051 A1 ML ...

Page 3: ...525 469 Ø8 1283 895 30 30 437 OP HPMP050 064 OP HPZP050 064 OP HPUS026 038 LPZP013 018 Instructions Danfoss DCS CC 2017 03 3 FRCC PI 051 A1 ML ...

Page 4: ...prightposition Store the unit between 35 C and 50 C Don t expose the packaging to rain or corrosive atmosphere After unpacking check that the unit is com plete and undamaged 3 Installation precautions Do not braze as long the condensing unit is under pressure Never place the unit in a flammable atmosphere Place the unit in such a way that it is not blocking orhinderingwalkingareas doors windowsors...

Page 5: ...nergize the unit It must start promptly If the compressor does not start check wiring conformity voltage on terminals and sequence phase Eventual reverse rotation of a 3 phase com pressor can be detected by following phe nomena unit doesn t start the compressor doesn t build up pressure it has abnormally high sound level and abnormally low power consumption In such case shut down the unit immediat...

Page 6: ...TER RL RELE RELAY V VENTILADOR FAN FUSÍVEL FUSIBLE FUSE C R 2 4 1 3 6 a2 5 a1 K PL PH 230V 1 50 60Hz PE RC F2 F3 CP S P PE 2 1 4 P L2 2 L1 V1 CV 1 2 5 CS CR RL 1 PE CV V2 F1 COMPRESSOR COMPRESOR CR CAPACITOR MARCHA RUN CS CAPACITOR ARRANQUE START CV CAPACITOR VENTILADOR FAN F CP FUSÍVEL FUSIBLE FUSE K CONTATOR CONTACTOR PH PRESSOSTATO ALTA PRESOSTATO ALTA PRESSURE SWITCH HBP PL PRESSOSTATO BAIXA P...

Page 7: ... FAN FUSÍVEL FUSIBLE FUSE 2 4 1 3 6 a2 5 a1 K PL PH 230V 3 50 60Hz PE F2 F3 CP P PE 2 1 4 P L2 L3 2 L1 V1 CV 1 RC PE CV V2 SFF M1 L N M2 L1 L2 L3 S1 S2 R1 1 8KOhm DEP 101B F1 COMPRESSOR COMPRESOR CR CAPACITOR MARCHA RUN CS CAPACITOR ARRANQUE START CV CAPACITOR VENTILADOR FAN F CP FUSÍVEL FUSIBLE FUSE K CONTATOR CONTACTOR PH PRESSOSTATO ALTA PRESOSTATO ALTA PRESSURE SWITCH HBP PL PRESSOSTATO BAIXA ...

Page 8: ...RANQUE START CV CAPACITOR VENTILADOR FAN F CP FUSÍVEL FUSIBLE FUSE K CONTATOR CONTACTOR PH PRESSOSTATO ALTA PRESOSTATO ALTA PRESSURE SWITCH HBP PL PRESSOSTATO BAIXA PRESOSTATO BAJA PRESSURE SWITCH LBP RC RESISTÊNCIA CARTER CALENTADOR CARTER CRANKCASE HEATER RL RELE RELAY V VENTILADOR FAN Code V HPMP HPZP LPZP Code V HPUS LPZS Danfoss can accept no responsibility for possible errors in catalogues b...

Page 9: ...Manipule la unidad con cuidado El embalaje admite el uso de una carretilla elevadora o una transpaleta para su manipulación Use siempre equipos de elevación adecuados y seguros Almacene y transporte la unidad en posición vertical Almacene la unidad a temperaturas compren didas entre 35 C y 50 C No exponga el embalaje a la lluvia o a atmósfe ras de carácter corrosivo Tras desembalar la unidad compr...

Page 10: ...y la fuente de ali mentación sean compatibles Compruebe que la resistencia de cárter se en cuentre en funcionamiento Compruebe que el ventilador pueda girar libre mente Compruebe que se haya retirado la chapa de pro tección de la parte posterior del condensador Equilibre las presiones de los lados HP y LP Ponga en marcha la unidad Debe arrancar de inmediato Si el compresor no se pone en mar cha co...

Page 11: ...ER RL RELE RELAY V VENTILADOR FAN FUSÍVEL FUSIBLE FUSE C R 2 4 1 3 6 a2 5 a1 K PL PH 230V 1 50 60Hz PE RC F2 F3 CP S P PE 2 1 4 P L2 2 L1 V1 CV 1 2 5 CS CR RL 1 PE CV V2 F1 COMPRESSOR COMPRESOR CR CAPACITOR MARCHA RUN CS CAPACITOR ARRANQUE START CV CAPACITOR VENTILADOR FAN F CP FUSÍVEL FUSIBLE FUSE K CONTATOR CONTACTOR PH PRESSOSTATO ALTA PRESOSTATO ALTA PRESSURE SWITCH HBP PL PRESSOSTATO BAIXA PR...

Page 12: ...FAN FUSÍVEL FUSIBLE FUSE 2 4 1 3 6 a2 5 a1 K PL PH 230V 3 50 60Hz PE F2 F3 CP P PE 2 1 4 P L2 L3 2 L1 V1 CV 1 RC PE CV V2 SFF M1 L N M2 L1 L2 L3 S1 S2 R1 1 8KOhm DEP 101B F1 COMPRESSOR COMPRESOR CR CAPACITOR MARCHA RUN CS CAPACITOR ARRANQUE START CV CAPACITOR VENTILADOR FAN F CP FUSÍVEL FUSIBLE FUSE K CONTATOR CONTACTOR PH PRESSOSTATO ALTA PRESOSTATO ALTA PRESSURE SWITCH HBP PL PRESSOSTATO BAIXA P...

Page 13: ...FAN FUSÍVEL FUSIBLE FUSE 5 6 2 4 1 3 6 a2 5 a1 K V2 CV PL PH 380V 3 50 60Hz PE F2 CP P PE 2 1 4 P L2 L3 1 2 L1 N V1 CV RC PE SFF M1 L N M2 L1 L2 L3 S1 S2 R1 1 8KOhm DEP 101B F1 COMPRESSOR COMPRESOR CR CAPACITOR MARCHA RUN CS CAPACITOR ARRANQUE START CV CAPACITOR VENTILADOR FAN F CP FUSÍVEL FUSIBLE FUSE K CONTATOR CONTACTOR PH PRESSOSTATO ALTA PRESOSTATO ALTA PRESSURE SWITCH HBP PL PRESSOSTATO BAIX...

Page 14: ...pós desembalar certifique se de que a unidade esteja completa e intacta 3 Medidas de segurança antes da montagem Nãosoldeaunidadecondensadoraenquanto ela estiver pressurizada Nunca instale a unidade em atmosferas inflamáveis Instaleaunidadedemodoqueestanãobloqueie nem atrapalhe áreas de passagem portas janelas e afins Certifique se de que haja espaço suficiente ao redor da unidade para circulação ...

Page 15: ...ediatamente Em caso negativo verifique as fiações a tensão nos terminais e a fase de sequência A eventual rotação inversa de um compressor trifásico pode ser detectada pelos seguintes fenômenos a unidade não inicia o compressor não gera pressão apresenta nível de ruído mais alto e consumo de energia mais baixo do que os normais Neste caso desligue o aparelho imediatamente e conecte as fases nos re...

Page 16: ...ATER RL RELE RELAY V VENTILADOR FAN FUSÍVEL FUSIBLE FUSE C R 2 4 1 3 6 a2 5 a1 K PL PH 230V 1 50 60Hz PE RC F2 F3 CP S P PE 2 1 4 P L2 2 L1 V1 CV 1 2 5 CS CR RL 1 PE CV V2 F1 COMPRESSOR COMPRESOR CR CAPACITOR MARCHA RUN CS CAPACITOR ARRANQUE START CV CAPACITOR VENTILADOR FAN F CP FUSÍVEL FUSIBLE FUSE K CONTATOR CONTACTOR PH PRESSOSTATO ALTA PRESOSTATO ALTA PRESSURE SWITCH HBP PL PRESSOSTATO BAIXA ...

Page 17: ... FAN FUSÍVEL FUSIBLE FUSE 2 4 1 3 6 a2 5 a1 K PL PH 230V 3 50 60Hz PE F2 F3 CP P PE 2 1 4 P L2 L3 2 L1 V1 CV 1 RC PE CV V2 SFF M1 L N M2 L1 L2 L3 S1 S2 R1 1 8KOhm DEP 101B F1 COMPRESSOR COMPRESOR CR CAPACITOR MARCHA RUN CS CAPACITOR ARRANQUE START CV CAPACITOR VENTILADOR FAN F CP FUSÍVEL FUSIBLE FUSE K CONTATOR CONTACTOR PH PRESSOSTATO ALTA PRESOSTATO ALTA PRESSURE SWITCH HBP PL PRESSOSTATO BAIXA ...

Page 18: ... FAN FUSÍVEL FUSIBLE FUSE 5 6 2 4 1 3 6 a2 5 a1 K V2 CV PL PH 380V 3 50 60Hz PE F2 CP P PE 2 1 4 P L2 L3 1 2 L1 N V1 CV RC PE SFF M1 L N M2 L1 L2 L3 S1 S2 R1 1 8KOhm DEP 101B F1 COMPRESSOR COMPRESOR CR CAPACITOR MARCHA RUN CS CAPACITOR ARRANQUE START CV CAPACITOR VENTILADOR FAN F CP FUSÍVEL FUSIBLE FUSE K CONTATOR CONTACTOR PH PRESSOSTATO ALTA PRESOSTATO ALTA PRESSURE SWITCH HBP PL PRESSOSTATO BAI...

Page 19: ...anfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trade marks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved ...

Reviews: