6
DKDHR
VI.GP.B1.02
Danfoss District Energy
Instructions
Kompakt H 28/35/42
6.0 Main components
6.1 H 228 ECL 200/P30
1
Plate heat exchanger
8
Circulation pump, HE (P1)
24 Fitting piece for heat meter
25 Electronic control
29 Actuator AMV(10/20) (M1)
30 Flow controller with integrated control valve AVQM
Please note:
Your substation may look different than the substation shown, as
variants with other components may be supplied. The control func-
tion, however, is basically as stated in this instruction manual.
Instructions for the fitted components will be supplied together with
the substation.
24
1
25
8
29
30
24
Primary
Secundary
Cylinder supply
Cylinder r
etur
n
HE r
etur
n
HE supply
DH supply
DH r
etur
n
6.1.1 Measurements
Dimensions without cover
H1350 x Wmax. 917 x D380 mm
6.1.2 Connections
Order:
1
District heating (DH) supply
2
District heating (DH) return
3
Heating (HE) supply
4
Heating (HE) return
5
Cylinder supply
6
Cylinder return
Connection sizes (example:
DH:
G1¼ (ET)
HE:
G1¼ (IT)
Cylinder:
G1” (ET)
Please note:
The connection sizes are adapted to the pipe dim. as follows:
Pipe dim. 28 mm: 1¼ connection
Pipe dim. 35 mm: 1½” connection
Pipe dim. 42 mm: 2” connection