7.9 Heat meters, Fitting pieces
The substation is equipped with fitting pieces for heat meters in
district heating supply and district heating return.
Assembly of heat meters
- Loosen nuts from fitting piece.
Remove fitting piece and replace with heat meter.
- do not forget gaskets.
- After mounting of heat meter remember to check and tighten
all threaded connections.
7.10 Mounting of outdoor temperature sensor (S1)
The outdoor temperature sensor is delivered separately and must
be mounted on site according to the enclosed illustrations.
The outdoor sensor is always to be mounted on the coldest side of
the property (normally the north side of the property).
The sensor must not be exposed to the morning sun, and should
not be mounted above windows, doors, air vents or other heat
sources, and not under balconies and roof eaves.
Mounting height approx. 2.5 m above ground.
Temperature range: -50 to 50° C
Electrical connections
Two wire non polarized (can be crossed)
Sensor cable: 2 x 0.4 - 1.5 mm²
Connect the cable ends to ECL controller in clamps 17 and 16.