4 PROFINET Configuration
4.1 Configuring the Ethernet Interface
The X1 and X2 interfaces are internally connected with an Ethernet switch and share the same physical MAC layer, and the same IP
settings apply to both interfaces.
IPv4 settings are configured in MyDrive
®
Insight or in the control panel.
Configure IPv4 settings.
In MyDrive
®
Insight, go to
Setup and Service
→
Interface configuration
→
Interface X1/X2
→
IPv4 settings
.
In the control panel, navigate to parameter group
10.2 Communication Interfaces
.
Table 10: IPv4 Settings
Function
Value
Description
Interface X1/X2
MAC address
00:1B:08:xx:xx:xx
The MAC address of interface X1/X2. The value is read-only.
IPv4 addressing
method
Disable
Only link-local IP address in the 169.254.xxx.xxx range is active.
Static IP
A static IP address is entered manually.
Automatic
IP address is assigned via a DHCP or BOOTP server.
DCP (default)
DCP is used with PROFINET where a PLC assigns the IP address, subnet
mask and other relevant parameters.
Requested IPv4
address
xxx.xxx.xxx.xxx
If
Automatic
is selected as the IPv4 addressing method and no DHCP/
BOOTP server is present, the X1/X2 interface automatically configures an IP
address and subnet mask in the 169.254.xxx.xxx range.
Requested IPv4
subnet mask
xxx.xxx.xxx.xxx
The requested IPv4 subnet mask for the interface.
Requested IPv4
gateway address
xxx.xxx.xxx.xxx
Requested IPv4 gateway address for the interface.
Enable ACD
Enable/disable (de-
fault)
Request to enable or disable Address Conflict Detection for the interface.
The change will not take effect before a power cycle is performed. If no
conflicts are detected, ACD activity displays 0. If an address conflict occurs,
the ACD activity will display 1, and the IPv4 interface will revert to an auto-
matically assigned IP address in the 169.254.xxx.xxx range.
Recommended setting for PROFINET is disabled.
DNS server 1, 2
xxx.xxx.xxx.xxx
The user-requested Domain Name Server 1 for the interface (for manual IP
addressing mode only).
4.2 Configuring PROFINET Name of Station
Navigate to parameter
10.3.2.2.1 Name of Station
.
Table 11: PROFINET Configuration, Name of Station
Menu in-
dex
Parame-
ter name
Parame-
ter num-
ber
Value
Additional informa-
tion
10.3.2.2.1
Name of
Station
7080
Accepted characters:
Each PROFINET de-
vice is identified with
a unique Name of
Station.