Table 13: General Connectivity Parameters
Menu in-
dex
Parameter
Param-
eter
num-
ber
Value
Description
10.3.1.2
Fieldbus profile
1301
iC Speed Profile (default)
PROFIdrive Standard telegram 1
Select the fieldbus profile. The se-
lection affects the interpretation of
the control word and status word.
10.3.1.3
Fieldbus Fault
Response
1303
Info (default)
Warning
Fault, Ramp to Coast
Fault, coast
See
for descriptions of the events.
Select the behavior when a field-
bus fault, for example loss of I/O
connection occurs.
10.3.1.4
No Fieldbus
Connection Re-
sponse
1327
Info (default)
Warning
Fault, Ramp to Coast
Fault, coast
See
for descriptions of the events.
Select the response in case there is
no fieldbus connection.
10.3.1.6
Process Data
Timeout Time
1340
0.05–18000 s (Default value: 1.00 s)
Set the timeout time. If process da-
ta is not received within the time
set, a process data timeout is trig-
gered.
10.3.1.12
Process Data
Timeout Re-
sponse
1341
Info
Warning
Warning – Change Control Place
Warning – Change Control Place Persistent
Fault, Ramp to coast
Fault (default)
See
for descriptions of the events.
Select the response in case there is
no fieldbus connection.
10.3.1.13
Process Data
Timeout Con-
trol Place
112
Local control (default)
Fieldbus control
I/O control
Advanced control
See
for descriptions of the control places.
Select the alternate control place
to be used if there is a fieldbus
timeout. This is only valid with a
timeout warning or info.
Table 14: Event Descriptions
Value
Description
Info
The event is logged in the event log.
Warning
The drive issues a warning.
Fault, ramp to coast
The drive issues a fault, ramps down, and coasts.
AQ408626183394en-000101 / 136R0280 | 25
Danfoss A/S © 2023.06
PROFINET Configuration
iC7 Series PROFINET
Operating Guide