5 Technical Data
5.1 Specifications
5.1.1 Inverter Specifications
Nomen-
clature
Parameter
FLX series
5
6
7
8
9
AC
|S|
Rated apparent
power
5 kVA
6 kVA
7 kVA
8 kVA
9 kVA
P
ac,r
Rated active power
1)
5 kW
6 kW
7 kW
8 kW
9 kW
Active power at
cos(phi)=0.95
4.75 kW
5.7 kW
6.65 kW
7.6 kW
8.55 kW
Active power at
cos(phi)=0.90
4.5 kW
5.4 kW
6.3 kW
7.2 kW
8.1 kW
Reactive power
range
0 - 3.0 kVAr
0 - 3.6 kVAr
0 - 4.2 kVAr
0 - 4.8 kVAr
0 - 5.4 kVAr
V
ac,r
Nominal AC voltage
(AC voltage range)
3P+N+PE - 230/400 V (+/- 20 %)
Rated current AC
3 x 7.2 A
3 x 8.7 A
3 x 10.1 A
3 x 11.6 A
3 x 13 A
I
acmax
Max. current AC
3 x 7.5 A
3 x 9.0 A
3 x 10.6 A
3 x 12.1 A
3 x 13.6 A
AC current distortion
(THD at nominal
output power, %)
-
-
-
-
-
Inrush current
9.5 A / 10 ms
cosphi
ac,r
Power factor at
100% load
>0.99
Controlled power
factor range
0.8 over-excited
0.8 under-excited
Standby
consumption
2.7 W
f
r
Nominal grid
frequency (range)
50 (
±
5 Hz)
DC
Max. PV input power
per MPPT
5.2 kW
6.2 kW
7.2 kW
8 kW
Nominal power DC
5.2 kW
6.2 kW
7.2 kW
8.3 kW
9.3 kW
V
dc,r
Nominal voltage DC
715 V
V
dcmin
/
V
mppmin
-
V
mppmax
MPP voltage - active
tracking
2)
/ rated
power
3)
220/250 - 800 V
220/260 - 800 V
220/300 - 800 V
220/345-800 V
220/390 - 800 V
MPP efficiency, static
99.9%
MPP efficiency,
dynamic
99.7%
V
dcmax
Max. DC voltage
1000 V
V
dcstart
Turn on voltage DC
250 V
V
dcmin
Turn off voltage DC
220 V
I
dcmax
Max. MPP current
12 A per PV input
Technical Data
34
L00410568-02_02 / Rev. date: 2013-12-10
5
5