Enclosure
size
Power [kW]
Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Moeller
Max trip level [A]
A2
0-75-4.0
gG-10
gG-25
PKZM0-25
25
A3
5.5-7.5
gG-10 (5.5)
gG-16 (7.5)
gG-32
PKZM0-25
25
B3
11-15
gG-25 (11)
gG-32 (15)
gG-63
PKZM4-50
50
B4
18.5-30
gG-40 (18.5)
gG-50 (22)
gG-63 (30)
gG-125
NZMB1-A100
100
C3
37-45
gG-63 (37)
gG-100 (45)
gG-150
NZMB2-A200
150
C4
55-75
aR-160 (55)
aR-200 (75)
aR-250
NZMB2-A250
250
A5
0.75-7.5
gG-10 (0.75-5.5)
gG-16 (7.5)
gG-32
PKZM0-25
25
B1
11-18
gG-25 (11)
gG-32 (15)
gG-40 (18.5)
gG-80
PKZM4-63
63
B2
22-30
gG-50 (22)
gG-63 (30)
gG-100
NZMB1-A100
100
C1
37-55
gG-63 (37)
gG-100 (45)
aR-160 (55)
gG-160 (37-45)
aR-250 (55)
NZMB2-A200
160
C2
75
aR-200 (75)
aR-250
NZMB2-A250
250
Table 10.16 525-600 V, Frame Sizes A, B and C
Enclosure
size
Power [kW]
Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Moeller
Max trip level [A]
A3
1.1
1.5
2.2
3
4
5.5
7.5
gG-6
gG-6
gG-6
gG-10
gG-10
gG-16
gG-16
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
-
-
B2
11
15
18
22
gG-25 (11)
gG-32 (15)
gG-32 (18)
gG-40 (22)
gG-63
-
-
C2
30
37
45
55
75
gG-63 (30)
gG-63 (37)
gG-80 (45)
gG-100 (55)
gG-125 (75)
gG-80 (30)
gG-100 (37)
gG-125 (45)
gG-160 (55-75)
-
-
C3
37
45
gG-80
gG-100
gG-100
gG-125
-
-
Table 10.17 525-690 V, Frame Sizes A, B and C