Environment
Enclosure
IP20
1)
/Type 1, IP21
2)
/Type 1, IP55/Type 12, IP66
Vibration test
1.0 g
Max. THVD
10%
Max. relative humidity
5% - 93% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test
class Kd
Ambient temperature
3)
Max. 50
°
C (24-hour average maximum 45
°
C)
1)
Only for
≤
3.7 kW (200-240 V),
≤
7.5 kW (400-480/500 V)
2)
As enclosure kit for
≤
3.7 kW (200-240 V),
≤
7.5 kW (400-480/500 V)
3)
Derating for high ambient temperature, see special conditions in the Design Guide
Minimum ambient temperature during full-scale operation
0
°
C
Minimum ambient temperature at reduced performance
- 10
°
C
Temperature during storage/transport
-25 to +65/70
°
C
Maximum altitude above sea level without derating
1000 m
Derating for high altitude, see special conditions in the Design Guide.
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
See section on special conditions in the Design Guide.