![background image](http://html1.mh-extra.com/html/danfoss/fc-300/fc-300_operating-instructions-manual_3464890076.webp)
P37K
P45K
P55K
P75K
High/Normal Load
1)
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft Output [kW]
37
45
45
55
55
75
75
90
Enclosure IP21, IP55, IP66
C1
C1
C1
C2
C2
Enclosure IP20
C3
C3
C3
C4
C4
Output current
Continuous (3x525-550 V) [A]
54
65
65
87
87
105
105
137
Intermittent (3x525-550 V) [A]
81
72
98
96
131
116
158
151
Continuous (3x525-600 V) [A]
52
62
62
83
83
100
100
131
Intermittent (3x525-600 V) [A]
78
68
93
91
125
110
150
144
Continuous kVA (550 V AC) [kVA]
51.4
61.9
61.9
82.9
82.9
100.0
100.0
130.5
Continuous kVA (575 V AC) [kVA]
51.8
61.7
61.7
82.7
82.7
99.6
99.6
130.5
Max. input current
Continuous at 550 V [A]
49
59
59
78.9
78.9
95.3
95.3
124.3
Intermittent at 550 V [A]
74
65
89
87
118
105
143
137
Continuous at 575 V [A]
47
56
56
75
75
91
91
119
Intermittent at 575 V [A]
70
62
85
83
113
100
137
131
Additional specifications
IP20 max. cable cross-section
5)
(mains and
motor)
50 (1)
150 (300 MCM)
IP20 max. cable cross-section
5)
(brake and
load sharing)
50 (1)
95 (4/0)
IP21, IP55, IP66 max. cable cross-section
5)
(mains, motor) [mm
2
(AWG)]
2)
50 (1)
150 (300 MCM)
IP21, IP55, IP66 max. cable cross-section
5)
(brake, load sharing) [mm
2
(AWG)]
2)
50 (1)
95 (4/0)
Max cable size with mains disconnect
[mm
2
(AWG)]
2)
50, 35, 35
(1, 2, 2)
95, 70, 70
(3/0, 2/0, 2/0)
185, 150, 120
(350MCM, 300MCM,
4/0)
Estimated power loss at rated max. load
[W]
4)
850
1100
1400
1500
Weight, enclosure IP20 [kg]
35
35
50
50
Weight, enclosure IP21, IP55 [kg]
45
45
65
65
Efficiency
4)
0.98
0.98
0.98
0.98
Table 10.9 Mains Supply 3x525-600 V AC (FC 302 only)
Specifications
VLT
®
AutomationDrive Operating
Instructions
72
MG33AM02 - VLT
®
is a registered Danfoss trademark
10
10