6-60 Terminal X30/8 Output
Option:
Function:
[0]
*
No operation
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor Current
[104]
Torque re. to lim.
[105]
Torque rel. to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[113]
Ext. Closed Loop 1
[114]
Ext. Closed Loop 2
[115]
Ext. Closed Loop 3
[130]
Output freq. 4-20 mA
[131]
Reference 4-20 mA
[132]
Feedback 4-20 mA
[133]
Motor cur. 4-20 mA
[134]
Torq. % lim 4-20 mA
[135]
Torq. % nom 4-20 mA
[136]
Power 4-20 mA
[137]
Speed 4-20 mA
[138]
Torque 4-20 mA
[139]
Bus Ctrl 0-20 mA
[140]
Bus Ctrl 4-20 mA
[141]
Bus Ctrl timeout 0-20
mA
[142]
Bus Ctrl timeout 4-20
mA
[143]
Ext. Closed Loop 1 4-20
mA
[144]
Ext. Closed Loop 2 4-20
mA
[145]
Ext. Closed Loop 3 4-20
mA
6-61 Term. X30/8 Output Min Scale
Range:
Function:
0%
*
[0.00 - 200 %]
Scales the minimum output of the selected analog signal on terminal X30/8. Scale the minimum value as a
percentage of the maximum signal value, i.e. 0 mA (or 0 Hz) is desired at 25% of the maximum output value
and 25% is programmed. The value can never be higher than the corresponding setting in par. 6-62 if value is
below 100%.
This parameter is active when option module MCB 101 is mounted in the frequency converter.
6-62 Term. X30/8 Output Max Scale
Range:
Function:
100%
*
[0.00 - 200 %]
Scales the maximum output of the selected analog signal on terminal X30/8. Scale the value to the desired
maximum value of the current signal output. Scale the output to give a lower current than 20 mA at full scale or
3. Parameter Description