Date format will depend on setting in par. 0-71,
Date Format
, and time format on setting in par. 0-72,
Time
Format
.
NB!
The frequency converter has no back up of the clock function and the set date/time will reset to default (2000-01-01 00:00) after a
power down unless a Real Time Clock module with back up is installed. Consequently the logging will be stopped until date/time is
readjusted in par. 0-70,
Set Date and Time
. In par. 0-79,
Clock Fault
, it is possible to program for a Warning in case clock not has been
set properly, e.g. after a power down.
NB!
When mounting an Analog I/O MCB109 option card, a battery back up of the date and time is included.
23-64 Timed Period Stop
Range:
Function:
2000-01-01 00:00
*
[2000-01-01
00:00 - 2099-12-31 23:59]
Set the date and time at which the Trend Analyses must stop update of the Timed Bin counters.
Date format will depend on setting in par. 0-71,
Date Format
, and time format on setting in par. 0-72,
Time
Format
.
NB!
When mounting an Analog I/O MCB109 option card, a battery back up of the date and time is included.
23-65 Minimum Bin Value
Range:
Function:
[0 - 100%]
Array with 10 elements ([0]-[9] below parameter number in display). Press OK and step between elements by
means of
▲
and
▼
buttons on the LCP.
Set the minimum limit for each interval in par. 23-61,
Continuous Bin Data
, and par. 23-62,
Timed Bin Data
.
Example: if selecting
counter
[1] and changing setting from 10% to 12%,
counter
[0] will be based on the interval
0 - <12% and
counter
[1] on interval 12% - <20%.
23-66 Reset Continuous Bin Data
Option:
Function:
Select
Do reset
[1] to reset all values in par. 23-61,
Continuous Bin Data
.
After pressing OK the setting of the parameter value will automatically change to
Do not reset
[0].
[0]
*
Do not reset
[1]
Do reset
23-67 Reset Timed Bin Data
Option:
Function:
Select
Do reset
[1] to reset all counters in par. 23-62,
Timed Bin Data
.
After pressing OK the setting of the parameter value will automatically change to
Do not reset
[0].
[0]
*
Do not reset
[1]
Do reset
VLT
®
HVAC Drive Programming Guide
3. Parameter Description
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
199
3