0-43 [Reset] Key on LCP
Option:
Function:
[0]
Disabled
No function
[1]
*
Enabled
[Reset] Key is enabled
[2]
Password
Avoid unauthorized resetting. If par. 0-43 is included in the My Personal Menu, then define the password in
par.
0-65, Personal Menu Password
. Otherwise define the password in
par. 0-60, Main Menu Password
.
3.2.7. 0-5* Copy / Save
Copy parameter settings between set-ups and to/from the LCP.
0-50 LCP Copy
Option:
Function:
[0]
*
No copy
No function
[1]
All to LCP
Copies all parameters in all set-ups from the frequency converter memory to the LCP memory. For service
purposes it is recommended to copy all parameters to the LCP after commissioning.
[2]
All from LCP
Copies all parameters in all set-ups from the LCP memory to the frequency converter memory.
[3]
Size indep. from LCP
Copies only the parameters that are independent of the motor size. The latter selection can be used to pro-
gramme several frequency converters with the same function without disturbing motor data which are already
set.
This parameter cannot be adjusted while the motor is running.
0-51 Set-up Copy
Option:
Function:
[0]
*
No copy
No function
[1]
Copy to set-up 1
Copies all parameters in the present edit set-up (defined in par. 0-11
Programming Set-up
) to Set-up 1.
[2]
Copy to set-up 2
Copies all parameters in the present edit set-up (defined in par. 0-11
Programming Set-up
) to Set-up 2.
[3]
Copy to set-up 3
Copies all parameters in the present edit set-up (defined in par. 0-11
Programming Set-up
) to Set-up 3.
[4]
Copy to set-up 4
Copies all parameters in the present edit set-up (defined in par. 0-11
Programming Set-up
) to Set-up 4.
[9]
Copy to all
Copies the parameters in the present set-up over to each of the set-ups 1 to 4.
3.2.8. 0-6* Password
Define password access to menus.
0-60 Main Menu Password
Option:
Function:
[100]
*
-9999 - 9999
Define the password for access to the Main Menu via the [Main Menu] key. If par. 0-61
Access to Main Menu
w/o Password
is set to
Full access
[0], this parameter will be ignored.
0-61 Access to Main Menu w/o Password
Option:
Function:
[0]
*
Full access
Disables password defined in par. 0-60
Main Menu Password
.
[1]
Read only
Prevent unauthorized editing of Main Menu parameters.
[2]
No access
Prevent unauthorized viewing and editing of Main Menu parameters.
[3]
Bus: Read only
Read only functions for parameters on fieldbus and/ or FC standard bus.
[4]
Bus: No access
No access to parameters is allowed via fieldbus and/ or FC standard bus.
[5]
All: Read only
Read only function for parameters on LCP, fieldbus or FC standard bus.
VLT
®
HVAC Drive Programming Guide
3. Parameter Description
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
35
3