Figure 31. Cable lug connection to the connection box (example only, the connection box may look
different)
9. Screw the cable gland to the connection box as shown in Figure below. Tighten the cable gland
from the cap of the gland. See Chapter
Tightening torques
.
Do not turn the body of the gland! By tightening from the cap of the gland the cable is sealed to the cable gland and at
the same time the cable gland is tightened to the connection box with correct torque.
10. Tighten the cable lug. Use tightening torque of 15 Nm.
11. Repeat the procedure to the other cables.
11. Repeat the procedure to the other cables and connection box (if the machine includes DUAL
option).
12. Check that the phase connections order in the connection box is correct, ie. corresponding
phases between the inverter and the machine are connected (U, V, W correspond to the L1, L2, L3
phases).
13. Close the connection box. Tighten the connection box cover screws. See chapter
Tightening
torques
. Use thread locking compound that makes it possible to remove the screws. (For example
Loctite 221).
Check the power cable shield grounding, see Chapter
Grounding connections
.
EM-PMI375
6. Installation