background image

 EKC 347 

Instructions  RI8BY553 DKRCC.PI.RP0.A1.ML / 520H4018 ©  Danfoss  01/2011 

9

*) This setting will only be possible if a data communication module has been 
installed in the controller.

Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep both buttons depressed at the same time as you recon nect the supply voltage

Error messages

The controller can give the following messages:

E1

Error message

Errors in the controller

E12

The external reference contribution is outside 
the range

E21

Level signal outside the range 1)

E22

Signal from ICM/ICAD outside the range

A1

Alarm message

Upper level limit reached

A2

Lower level limit reached

A3

Alarm level limit reached

Continued from previous page

1)
If E21 is detected. EKC 347 will force the valve to close or open the valve depending 
af n35

If Low presure has been selected. (n35=0)
The valve is forced to fully closed, however if Min. Opening Degree (n33) is higher 
than 0 the valve will open to the value of n33

If High presure has been selected. (n35=1)
The valve is forced to fully open, however if Max. Opening Degree (n32) is lower than 
100 the valve will open to the value of n32

Define the input signal on terminals 10, 20, 21 (external 
reference displacement)
0: OFF
1: 4-20 mA
2: 0-20 mA
3: 2-10 V
4: 0-10 V

o10

0

4

0

Language
0=English, 1=German, 2=Frensh, 3=Danish, 4=Spanish, 
5=Italian, 6=Swedish. When you change the setting 
you must also activate o04.

o11* 0

6

0

Set supply voltage frequency

o12

0/50 
Hz

1/60 
Hz

0

Selection of parameter for display and AO (except from 
when o09=1,2 or 5)
If o34 = 0:
0:  Liquid level is show
1:  Valve’s opening degree OD will be shown
If o34 = 1:
0:  Liquid level is show
1:  The ICM valve position feed back signal [%] will be 
shown

o17

0

1

0

Manual control of outputs:
OFF:  No manual control
1: Upper level relay put in pos. ON
2: Lower level relay put in pos.  ON
3: AKV/A output put in pos. ON
4: Alarm relay activated (cut out)

o18

OFF

4

0

Define input signal (level signal) on terminals 14, 15, 16
0: OFF
1: 4-20 mA
2: 0-10 V (also set the voltage values in the next two 
menus) 
Read functional description if the connection used is a 
master/slave function.

o31

0

2

1

Define input signal’s lower value for terminal 14, if 
required

o32

0.0 V

4.9 V

4.0

Define input signal’s upper value for terminal 14, if 
required

o33

5.0 V

10 V

6.0

Define input signal on terminals 17-18
0: Not used
1: ICM mA feedback signal from ICAD connected
2:  Not used

o34

0

2

0

Service

Read liquid level

u01

%

Read liquid level reference

u02

%

Read external contribution to the reference

u06

mA

Read external contribution to the reference

u07

V

Read current signal on the analog output

u08

mA

Read status of input DI

u10

Read valve’s opening degree

u24

%

Read level signal

u30

mA

Read level signal

u31

V

Read signal from ICM/ICAD

u32

mA

Read signal from ICM/ICAD converted into %

u33

%

Summary of Contents for EKC 347

Page 1: ...Identification Identification M l Dimensions Ma e Dimensions Instructions EKC 347 DKRCC PI RP0 A1 ML 01 2011 Princip Principle Montageprinzip Principe 084B7067 Type AKV AKVA...

Page 2: ...nce displacement 3 4 Data communication Mount only if a data communication module has been mounted It is important that the installation of the data communi cation cable be done correctly Cf separate...

Page 3: ...ange schlossen werden Es darf nur eines der beiden m glichen Ventiltypen ange schlossen werden Anwendungsbestimmte Anschl sse Klemme 12 13 Alarmrelais Siehe A19 und A18 8 10 Relais f r untere Niveaugr...

Page 4: ...EKC 347 Tilslutningseksempler Connection examples Anschlu beispiele Exemples de raccordement Ejemplo de conexiones EKC 347 ON OFF Application Open Close solenoid valve with coil 110 V Voltage 110 V a...

Page 5: ...NSK ON OFF anvendelse Udover modulerende PI regulering underst tter EKC 347 ogs ON OFF betjening med hysterese For at sikre denne betjening P Band skal v re n04 0 OFF Hysterese er givet ved n34 Setpoi...

Page 6: ...e bningsgrad skal du trykke kortvarigt p den nederste knap 0 Hvis du vil indstille det nskede setpunkt f r du adgang ved at trykke p begge knapper samtidigt 0 100 100 Niveaustyring Eksternt bidrag til...

Page 7: ...k 4 spansk 5 italiensk 6 svensk Hvis du ndrer denne indstilling skal du ogs aktivere o04 o11 0 6 0 Indstil forsyningssp ndingens frekvens o12 0 50 Hz 1 60 Hz 0 Valg af parameter for displayvisning og...

Page 8: ...you wish to see the actual opening degree give the lower button a brief push 0 If you wish to set the required setpoint you obtain ac cess by pushing both buttons simultaneously 0 100 100 Level contr...

Page 9: ...4 0 Language 0 English 1 German 2 Frensh 3 Danish 4 Spanish 5 Italian 6 Swedish When you change the setting you must also activate o04 o11 0 6 0 Set supply voltage frequency o12 0 50 Hz 1 60 Hz 0 Sel...

Page 10: ...des gemessenen Fl ssigkeitsniveaus 50 0 Zur Anzeige des aktuellen ffnungsgrads kurzzeitig die untere Taste bet tigen 0 Zugang zur Einstellung des gew nschten Sollw erts erh lt man durch gleichzeitige...

Page 11: ...andere Sprache einstellen m ssen Sie auch O04 aktivieren o11 0 6 0 Einstellung der Spannungsversorgungsfrequenz o12 0 50 Hz 1 60 Hz 0 Wahl der Parameter zur Displayanzeige und AO ausser wenn die eins...

Page 12: ...u de liquide mesur 50 0 Pour relever le degr d ouverture actuelle du d tendeur appuyez bri vement sur le bouton inf rieur 0 Pour r gler le point de consigne appuyez sur les deux boutons en m me temps...

Page 13: ...ue il faut galement action ner o04 o11 0 6 0 Choisir la fr quence d alimentations o12 0 50 Hz 1 60 Hz 0 Choix de param tre pour la visualisation et AO sauf si o09 1 2 ou 5 Si o34 0 0 affichage du nive...

Page 14: ...ra en cada momento pulsar el bot n inferior 0 Si se desea ajustar la referencia se puede acceder pulsando ambos botones simult neamente 0 100 100 Control de nivel Contribuci n externa a la referencia...

Page 15: ...osici n ON 3 Salida AKV A en posici n ON 4 Rel de alarma activado abierto o18 0 4 0 Definici n de la se al de entrada se al de nivel en terminales 14 15 16 0 OFF 1 4 20 mA 2 0 10 V ajustar tambi n los...

Page 16: ...Danfoss 01 2011 EKC 347 DE BD The Product contains electrical components And may not be disposed together with domestic waste Equipment must be separate collected with Electrical and Elec tronic wast...

Page 17: ...EKC 347 Instructions RI8BY553 DKRCC PI RP0 A1 ML 520H4018 Danfoss 01 2011 17...

Reviews: