Instructions  RI8BY553 DKRCC.PI.RP0.A1.ML / 520H4018 ©  Danfoss  01/2011 

   EKC 347

Menu survey

ENGLISH

Light-emitting diodes (LED) on front panel
There are LED’s on the front panel which will light up when the 
corresponding relay is activated.
The upper LED will indicate the valve’s opening degree. A short 
pulse indicates a slow liquid flow and a long pulse a fast liquid 
flow.
The three lowest LED’s will flash, if there is an error in the regula-
tion.
In this situation you can upload the error code on the display and 
cancel the alarm by giving the uppermost button a brief push.

Display
The values will be shown with three digits, and

 

after an opera-

tion the controller will return to its standard mode and show the 
measured liquid level.

Operation

The buttons
When you want to change a setting, the two buttons will give you 
a higher or lower value depending on the button you are push-
ing. But before you change the value, you must have access to the 
menu. You obtain this by pushing the upper button for a couple 
of seconds - you will then enter the column with parameter codes. 
Find the parameter code you want to change and push the two 
buttons simultaneously. When you have changed the value, save 
the new value by once more pushing the two buttons simultane-
ously.

 

Gives access to the menu (or cuts out an alarm)

 

Gives access to changes

 

Saves a change

Examples of operations

Set reference

1. Push the two buttons simultaneously
2. Push one of the buttons and select the new value
3. Push both buttons again to conclude the setting
 

Set one of the other menus

1. Push the upper button until a parameter is shown
2. Push one of the buttons and find the parameter you want to 

change

3. Push both buttons simultaneously until the parameter value is 

shown

4. Push one of the buttons and select the new value
5. Push both buttons again to conclude the setting

Literature survey:
  Manual for EKC 347 ..............................................................RS8AX---
  Instruction for EKC 347 .......................................................RI8BY---
  Installation guide, "Data communication link
  for ADAP-KOOL® " .................................................................RC8AC---

SW = 1.1x

Function

Pa-
ram-
eter

Min.

Max.

Fac.
set-
ting

Normal display
Read the measured liquid level

-

% 50.0

If you wish to see the actual opening degree, give the 
lower button a brief push

-

% 0

If you wish to set the required setpoint you obtain ac-
cess by pushing both buttons simultaneously

-

0%

100% 100

Level control
External contribution to the reference. Cf. also o10. 
Value is set in %-points.

r06

-100

100

0.0

Start / stop of level control

r12

OFF/0 ON/1

1

Alarm
Upper level limit

A01 0 %

100% 85

Lower level limit

A02 0%

100% 15

Time delay for upper level limit

A03 0 s

999 s

50

Time delay for lower level limit

A15 0 s

999 s

10

Level alarm limit

A16 0%

100% 20

Delay for level alarm

A17 0 s

999 s

0

The level alarm is linked to:
0:  Rising level (higher level than A16)
1:  Falling level (lower level than A16)
2: Same function as if A18=0.  When A2 alarm is gener-
ated and Relay for lower level limit, gives OFF signal 
(cut out).
3: Same function as if A18=1 When A2 alarm is gener-
ated and Relay for lower level limit, gives OFF signal 
(cut out).

A18 0

3

0

Function for Alarm relay when A1, A2 or A3 alarms are 
detected.
0: Alarm relay to be activated when A1 or A2 or A3 are 
detected.
1: Alarm relay only to be activated when A3 is detected.

A19 0

1

0

Regulating parameters
P - band

n04

0%/Off 200% 30

I: Integration time Tn

n05

60

600/
Off

400

Period time (only if AKV/A valve is used)

n13

3 s

10 s

6

Max. opening degree

n32

0%

100% 100

Min. opening degree

n33

0%

100% 0

Neutral zone (only for ICM valve)

n34

2%

25%

2

Definition of regulating principle
Low:  On the low-pressure side (valve closes when 
liquid level is rising)
High: On the high-pressure side (valve opens when 
liquid level is rising)

n35

Low/0 Hig/1 0

Miscellaneous
Controller's address

o03* 0

60

0

ON/OFF switch (service-pin message)

o04* OFF

ON

Define valve and output signal:
1: ICM. AO: 4-20 mA
2: ICM. AO: 0-20 mA
3: AKV/A, AO: 4-20 mA
4: AKV/A, AO: 0-20 mA
Or if a master/slave function is used:
5: AKV/A, MASTER
6: AKV/A, SLAVE 1/1. AO:4-20 mA
7: AKV/A, SLAVE 1/1. AO:0-20 mA
8: AKV/A, SLAVE 1/2. AO:4-20 mA
9: AKV/A, SLAVE 1/2. AO:0-20 mA
10: AKV/A, SLAVE 2/2. AO:4-20 mA
11: AKV/A, SLAVE 2/2. AO:0-20 mA
12: AKV/A, SLAVE 1/1. AO:4-20 mA - AO always updated
13: AKV/A, SLAVE 1/1. AO:0-20 mA- AO always updated
14: AKV/A, SLAVE 1/2. AO:4-20 mA- AO always updated
15: AKV/A, SLAVE 1/2. AO:0-20 mA- AO always updated
16: AKV/A, SLAVE 2/2. AO:4-20 mA- AO always updated
17: AKV/A, SLAVE 2/2. AO:0-20 mA- AO always updated

o09

1

17

1

Summary of Contents for EKC 347

Page 1: ...Identification Identification M l Dimensions Ma e Dimensions Instructions EKC 347 DKRCC PI RP0 A1 ML 01 2011 Princip Principle Montageprinzip Principe 084B7067 Type AKV AKVA...

Page 2: ...nce displacement 3 4 Data communication Mount only if a data communication module has been mounted It is important that the installation of the data communi cation cable be done correctly Cf separate...

Page 3: ...ange schlossen werden Es darf nur eines der beiden m glichen Ventiltypen ange schlossen werden Anwendungsbestimmte Anschl sse Klemme 12 13 Alarmrelais Siehe A19 und A18 8 10 Relais f r untere Niveaugr...

Page 4: ...EKC 347 Tilslutningseksempler Connection examples Anschlu beispiele Exemples de raccordement Ejemplo de conexiones EKC 347 ON OFF Application Open Close solenoid valve with coil 110 V Voltage 110 V a...

Page 5: ...NSK ON OFF anvendelse Udover modulerende PI regulering underst tter EKC 347 ogs ON OFF betjening med hysterese For at sikre denne betjening P Band skal v re n04 0 OFF Hysterese er givet ved n34 Setpoi...

Page 6: ...e bningsgrad skal du trykke kortvarigt p den nederste knap 0 Hvis du vil indstille det nskede setpunkt f r du adgang ved at trykke p begge knapper samtidigt 0 100 100 Niveaustyring Eksternt bidrag til...

Page 7: ...k 4 spansk 5 italiensk 6 svensk Hvis du ndrer denne indstilling skal du ogs aktivere o04 o11 0 6 0 Indstil forsyningssp ndingens frekvens o12 0 50 Hz 1 60 Hz 0 Valg af parameter for displayvisning og...

Page 8: ...you wish to see the actual opening degree give the lower button a brief push 0 If you wish to set the required setpoint you obtain ac cess by pushing both buttons simultaneously 0 100 100 Level contr...

Page 9: ...4 0 Language 0 English 1 German 2 Frensh 3 Danish 4 Spanish 5 Italian 6 Swedish When you change the setting you must also activate o04 o11 0 6 0 Set supply voltage frequency o12 0 50 Hz 1 60 Hz 0 Sel...

Page 10: ...des gemessenen Fl ssigkeitsniveaus 50 0 Zur Anzeige des aktuellen ffnungsgrads kurzzeitig die untere Taste bet tigen 0 Zugang zur Einstellung des gew nschten Sollw erts erh lt man durch gleichzeitige...

Page 11: ...andere Sprache einstellen m ssen Sie auch O04 aktivieren o11 0 6 0 Einstellung der Spannungsversorgungsfrequenz o12 0 50 Hz 1 60 Hz 0 Wahl der Parameter zur Displayanzeige und AO ausser wenn die eins...

Page 12: ...u de liquide mesur 50 0 Pour relever le degr d ouverture actuelle du d tendeur appuyez bri vement sur le bouton inf rieur 0 Pour r gler le point de consigne appuyez sur les deux boutons en m me temps...

Page 13: ...ue il faut galement action ner o04 o11 0 6 0 Choisir la fr quence d alimentations o12 0 50 Hz 1 60 Hz 0 Choix de param tre pour la visualisation et AO sauf si o09 1 2 ou 5 Si o34 0 0 affichage du nive...

Page 14: ...ra en cada momento pulsar el bot n inferior 0 Si se desea ajustar la referencia se puede acceder pulsando ambos botones simult neamente 0 100 100 Control de nivel Contribuci n externa a la referencia...

Page 15: ...osici n ON 3 Salida AKV A en posici n ON 4 Rel de alarma activado abierto o18 0 4 0 Definici n de la se al de entrada se al de nivel en terminales 14 15 16 0 OFF 1 4 20 mA 2 0 10 V ajustar tambi n los...

Page 16: ...Danfoss 01 2011 EKC 347 DE BD The Product contains electrical components And may not be disposed together with domestic waste Equipment must be separate collected with Electrical and Elec tronic wast...

Page 17: ...EKC 347 Instructions RI8BY553 DKRCC PI RP0 A1 ML 520H4018 Danfoss 01 2011 17...

Reviews: