VI.KT.G6.02 © Danfoss | 2016.05 | 13
Maintenance
Displace (parallel displacement)
2176
Setting range
Factory setting
-20 ... 20
0
Adjust the parallel displacement of the heat curve with a number of degrees, if required.
Whether it is reasonable to change the ‘Slope’ (at outdoor temperatures below 0 °C) or
parallel displacement (at outdoor temperatures above 0 °C) will depend on the individual
heat requirement.
Small increases or reductions in the heating temperature can be implemented by means of
the parallel displacement.
Temp. min. (flow temp. limit, min.)
2177
Setting range
Factory setting
10 ... 150 °C
10 °C
Choose the allowed min. flow temperature for your system. Adjust the factory setting, if
required.
Temp. max. (flow temp. limit, max.)
2178
Setting range
Factory setting
10 ... 150 °C
90 °C
Choose the allowed max. flow temperature for your system. Adjust the factory setting, if
required.
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.