VI.KT.G6.02 © Danfoss | 2016.05 | 31
Maintenance
Knee point
7162
Setting range
Factory setting
OFF / 30 ... 50 °C
40 °C
Choose the temperature at which the heat curve should bend.
OFF: Floor heating systems.
30 ... 50: Radiator systems.
Min. on time (min. activation time gear motor)
7189
Setting range
Factory setting
2 ... 50
10
The min. pulse length in milliseconds for activation of the gear motor.
Setting
Value x 20 ms
2
40 ms
10
200 ms
50
1000 ms
The setting should be kept as high as acceptable to increase the lifetime of the actuator.
Daylight (daylight saving time changeover)
7198
Setting range
Factory setting
ON / OFF
ON
Choose whether you want the change to summer / winter time to be automatic or manual.
ON:
The controller’s built-in clock automatically c / - one hour on the
standardized days for daylight saving time changeover for Central Europe.
OFF: You change manually between summer and winter time by setting the
clock backward or forward.
ECL address (master / slave address)
7199
Setting range
Factory setting
0 ... 15
15
This settting is relevant if more controllers are working in the same ECL Comfort system (connected via
the ECL BUS) and / or ECA units are connected.