VI.KT.G6.02 © Danfoss | 2016.05 | 21
Maintenance
Ramp (reference ramping)
5013
Setting range
Factory setting
OFF / 1 ... 99 m
OFF
The time in which the desired flow temperature increases gradually to avoid load peaks in the heat
supply.
Set the ramping time for the controller.
Temp. °C
Time (min.)
Setting line 5013
In order to avoid load peaks in the supply network, the flow temperature can be set to
increase gradually after a period with setback temperature. This causes the valve to open
gradually.
Optimizer (optimizing time constant)
5014
Setting range
Factory setting
OFF / 10 ... 59
OFF
Optimizes the start and stop times for the comfort temperature period to obtain the best comfort at the
lowest energy consumption. The lower the outdoor temperature, the earlier the heating cut-in.
Adjust the optimizing time constant.
The value consists of a two digit number. The two digits have the following meaning:
Left digit
Heat accumulation of the building
System type
1X
light
Radiator systems
2X
medium
3X
heavy
4X
medium
Floor heating systems
5X
heavy