63
VMBMA602
15 Troubleshooting
15.1 Alarm list
Shown in display in the event of an alarm. To reset alarms 1-5, set the operating mode to OFF or cut the power supply.
Message
Meaning
HIGHPRESS ERROR
Tripped high pressure switch. Compressor stopped. No hot water production.
LOWPRESS ERROR
Tripped low pressure switch. Compressor stopped. No hot water production.
MOTOR P ERROR
Deployed motor protection (Over current relay compressor). Compressor stopped. No hot
water production.
BRINE OUT
Brine out is less than the set minimum temperature. Compressor stopped. No hot water
production.
BRINEFLOW LOW
Flow sensor not active during last start. Compressor stopped. No hot water production.
ADD. HEAT
Overheating protection deployed. No additional heat.
SENSOR OUTDOOR
Fault in outside sensor. Zero degrees used for calculations.
SENSOR FRONT
Supply line sensor error. Everything stops except the heating system’s circulation pump.
SENSOR RETURN
Return sensor fault. Return temperature = Supply line – 5 is used. Calculated supply tem-
perature limited to maximum 45°C.
SENSOR HOT WATER
Fault on sensor for start temperature. No hot water production.
SENSOR DEFROST
Defrost sensor fault. Heat and hot water production is controlled from the outdoor sensor’s
value instead. (Applies to DHP-A, -AL)
MS FAN
Deployed motor protection for outdoor unit fan. Compressor stopped. No hot water pro-
duction. (Applies to DHP-A, -AL)
SENSOR COOLING
Sensor fault. Cooling function stops.
15.2 Measurement points
Conversion table for sensors
NOTE! When reading the resistance of the sensors, the sensor leads must first be disconnected from the control equipment.
Outdoor sensor
Other sensors
°C
ohm, Ω
°C
kilo ohm, kΩ
-30
1884
0
66.3
-25
1443
5
52.4
-20
1115
10
41.8
-15
868
15
33.5
-10
681
20
27.1
-5
538
25
22.0
0
428
30
18.0
5
343
35
14.8
10
276
40
12.2
15
224
45
10.1
20
183
50
8.5
25
150
55
7.1
30
124
60
6.0
35
103
65
5.0
40
86
70
4.2
75
3.7
80
3.1
85
2.7
90
2.3
95
2.0
1. Disconnect the sensor cable at the I/O card.
2. First measure the sensor including the cable.
3. Then measure the sensor only.