61
VMBMA602
Menu selection
Meaning
Factory setting
UNDER 5°C DEFR
Safety defrosting occurs when the outdoor temperature has been below 5° for a
set number of days, 20°C for 10 minutes.
7D
(interval: , 1D / 14D)
MIN TIME DEFROST
Minimum time between two defrosts in minutes.
45M
(interval: 10M / 60M)
DEFR SENSOR
Shows the actual temperature of the incoming air to the outdoor unit.
-
Sub menu SERVICE -> OPTI (
Opti models
)
The menu applies to Optimum models with speed controlled circulation pumps and only appears if ON in SERVICE -> INSTALLATION ->
SYSTEM -> ADDITION -> CONTROLLED CP menu is selected. Used to change the circulations pumps’ operating settings.
Menu selection
Meaning
Factory setting
TEMP DIFF CIRC.
Desired temperature difference between supply and return line for the heating
system..
8°C
(interval: , 0°C / 15°C)
TEMP DIFF BRINE
Desired temperature difference between supply and return line for the brine
system.
3°C
(interval: , 0°C / 15°C)
START FLOW CIRC.
Speed control of the heating system’s circulation pump in Volts. Higher voltage
gives a greater circulation pump speed, which gives a lower temperature differ-
ence. A low voltage gives a greater difference.
3 - 10 = Manually adjustable speed, where 3 is low voltage and 10 is high volt-
age.
7V (interval: 3V / 10V)
START FLOW BRINE
Speed control of the brine system’s circulation pump in Volts. Higher voltage
gives a greater brine pump speed, which gives a lower temperature difference. A
low voltage gives a greater difference.
3 - 10 = Manually adjustable speed, where 3 is low voltage and 10 is high volt-
age.
10V (interval: 3V / 10V)
CONST. FL. CIRC.
If TEMP DIFF CIRC is set to XX the flow is continuous with this value in the heat-
ing system. Value indicated in Volts.
7V (interval: 3V / 10V)
CONST. FL. BRINE
If TEMP DIFF BRINE is set to XX the flow is continuous with this value in the brine
system. Value indicated in Volts.
10V (interval: 3V / 10V)
MIN FLOW CIRC.
Lowest permitted voltage (speed) of the circulation pump’s flow in the heating
system. If there is no heat demand, there may still be a demand to read in the
temperatures for the sensors in the system and the circulation pump therefore
must be run.
3V (interval: 3V / 10V)-
MAX H.W CHARGE
Highest supply temperature during water heating.
55°C
(interval: 50°C / 65°C)
MIN H.W CHARGE
Lowest desired supply temperature during water heating.
50°C
(interval: 30°C / 65°C)
Sub menu SERVICE ->HGW
(DHP-H Opti Pro)
The menu applies to the DHP-H Opti Pro model with de-superheater and only appears if ON in SERVICE -> INSTALLATION -> SYSTEM ->
ADDITION -> HGW SHUNT menu is selected. Used to change the de-superheater’s operating settings.
Menyval
Betydelse
Fabriksinställning
HGW TEMP.
Shows the HGW sensor after the de-superheater (the supply temperature to
water heater) in °C.
-
TEMP DIFF.
Desired difference between the HGW sensor and water heater’s start sensor.
20K
(interval: 15K / 35K)
HOT WATER DIFF.
Shows actual difference between the HGW sensor and water heater’s start sen-
sor.
-
HOT WATER TO RAD.
If there is a heat demand, the HGW shunt switches to the heating system when
the weighted value is greater than the total of the START temperature for hot
water and this value. Example: 40°+3K = at a temperature of 43°C in the water
heater, the shunt switches to the heating system.
3K
(interval: 1K / 10K)