VMBMA602
Sub menu INFORMATION -> HEAT CURVE 2
The menu is active if the expansion card is installed and only appears if shunt group sensor is connected and activated in menu SERVICE ->
INSTALLATION -> SYSTEM -> SHUNTGROUP (Expansion card). Used to change settings for heat curve 2.
Menu selection
Meaning
Factory setting
CURVE 2
Calculated shunt group temperature at 0°C outdoor temperature. Shown as a
graph that also shows MIN and MAX values.
40°C
(interval: 22°C / 56°C)
MIN
Minimum permitted shunt group temperature, if the temperature for heat-stop
has not been reached.
10°C
(interval: 10°C / 50°C)
MAX
Maximum permitted shunt group temperature.
55°C
(interval: 15°C / 70°C)
Sub menu INFORMATION -> TEMPERATURE
Used to indicate the prevailing temperatures, history and set/calculated values. History can be accessed to view all the values by pressing
the right arrow to present a graph of the last 100 measurement points for the set time interval (SERVICE -> INSTALLATION -> LOGTIME). In
the event of an alarm, history stops being logged until the alarm is reset by changing the operating mode to OFF.
Menu selection
Meaning
Factory setting
OUTDOOR
Shows the actual outdoor temperature.
-
ROOM
Shows the actual set temperature.
-
Supply line
Shows the actual supply temperature. The calculated supply temperature to the
heating system group is within brackets.
During hot water production in operating mode ADD.HEAT the value for HOT
WATER STOPP + 5° is shown within brackets.
-
Return line
Shows the actual return temperature. The stop temperature, MAX RETURN is
within brackets.
-
HOT WATER
Shows the actual hot water temperature.
-
INTEGRAL
Shows the actual calculated value for integral.
-
BRINE OUT
Shows the actual temperature for brine out.
-
BRINE IN
Shows the actual temperature for brine in.
-
POOL
(Expansion card)
Only appears if POOL is selected. Shows the actual pool temperature. The set
pool temperature is shown in brackets.
-
SHUNTGROUP
(Expansion card)
Only appears if SHUNTGROUP is selected. Shows the actual supply temperature.
The calculated supply temperature to the shunt group is within brackets.
-
COOLING
(Expansion card)
Only appears if COOLING is selected. Shows the actual supply temperature. The
set point value is shown in brackets.
-
CURRENT
(Expansion card)
Only appears if CURRENT LIMITER is selected. Shows the actual current con-
sumption. The set value for MAX CURRENT is shown between brackets.
-
Sub menu INFORMATION -> OPERAT. TIME
Used to show the operating time for each component. Time given in hours.
Menu selection
Meaning
Factory setting
HEATPUMP
Compressor operating time for both heating and hot water production.
-
ADD. HEAT 1
Operating time auxiliary heater power stage 1 with full output 3 kW (VL).
-
ADD. HEAT 2
Operating time auxiliary heater power stage 2 with full output 6 kW (VL).
-
ADD.HEAT 3
(Defrost card)
Operating time auxiliary heater power stage 3 with full output 6 kW (VL).
-
HOT WATER
Operating time hot water with compressor.
-
COOLING
(Expansion card)
Operating time passive cooling.
-
COOLING ACTIVE
(Expansion card)
Operating time active cooling.
-