Diagram showing all electrical terminals.
Terminal 37 is the input to be used for Safe Stop.
Very long control cables and analog signals may
in rare cases and depending on installation result
in 50/60 Hz earth loops due to noise from mains
supply cables.
If this occurs, you may have to break the screen
or insert a 100 nF capacitor between screen and
chassis.
The digital and analog in- and outputs must be
connected separately to the CD302 common
inputs (terminal 20, 55, 39) to avoid ground cur-
rents from both groups to affect other groups.
For example, switching on the digital input may
disturb the analog input signal.
130BA025.17
91 (L1)
92 (L2)
93 (L3)
PE
88 (-)
89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
0/4-20 mA
12 (+24V OUT)
13 (+24V OUT)
37 (D IN)
18 (D IN)
20
(COM D IN)
10Vdc
15mA 130/200mA
+ -
+
-
(U) 96
(V) 97
(W) 98
(PE) 99
(COM A OUT) 39
(A OUT) 42
(P RS-485) 68
(N RS-485) 69
(COM RS-485) 61
0V
5V
S801
0/4-20 mA
RS-485
RS-485
03
+10Vdc
-10Vdc -
+10Vdc
+10Vdc
0/4-20 mA
-10Vdc -
240Vac, 2A
24Vdc
02
01
05
04
06
240Vac, 2A
24V (NPN)
0V (PNP)
0V (PNP)
24V (NPN)
19 (D IN)
24V (NPN)
0V (PNP)
27
24V
0V
(D IN/OUT)
0V (PNP)
24V (NPN)
(D IN/OUT)
0V
24V
29
24V (NPN)
0V (PNP)
0V (PNP)
24V (NPN)
33 (D IN)
32 (D IN)
12
ON
S201
ON
2
1
S202
ON/I=0-20mA
OFF/U=0-10V
95
400Vac, 2A
P 5-00
2
1
ON
S801
(R+) 82
(R-) 81
*
*
*
3 Phase
power
input
DC bus
Switch Mode
Power Supply
Motor
Analog Output
Interface
relay1
relay2
(PNP) = Source
(NPN) = Sink
ON=Terminated
OFF=Open
Brake
resistor
Instructions
AN000086420674en-000201 | 7
© Danfoss | DCS (CC) | 2019.04